Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why making capacity is more than breaking capacity?

Answer Posted / borys nijinski

The breaking capacity is less than make because make does
not require the arc to be extinguished. When the contacts
open, with current flowing, there is an arc created and
that arc needs to be extinguished. Extinguishing the arc
can be achieved by lengthening the arc (arc chute and air
puffer) or through an environment that does maskes the
creation of arcs difficult (eg SF6). AC arcs are much
easier to extinguish because the voltage passes through 0;
DC arcs are much harder to extinguish which is evidenced by
the lower rating of break capacity with DC as opposed to AC
for the same contactor/breaker.

Is This Answer Correct ?    3 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A 2083kva AVR was tested, phase to ground shows continuity, what is the implications

1082


what is the difference between neutral and earth

2181


How to know th details about an electrical Drawing ? Please mention the easy method.

2494


if the load is 80 amp for main fuse and 100 amp for breaker so how can we calculate the cable size (cooper ) .

2115


WHATIS TIME CONSTANT? WHATIS ITS SIGNIFICANCE? ILLUSTRATE THROUGH EXAMLES.

2304


What is the settings of distance protection relay in 400 kv line

1751


Is it posible to instal one more SMDB from the existing SMDB and is it practical.

2161


What is the capacity of the Fastners 12mm?

2504


I want to know the 'Test voltage' for Tandelta testing of 3.3 / 6.6 / 11 KV Motors. Please explain

2300


In which of the following case, the rotating magnetic field is reversed? A regenerative breaking B plugging C dynamic breaking D forward motoring

2009


What is minimum permicible value of leackage current for LT Panle when applying voltage up to 3 KV for 5 Minuits?

2304


Block diagram of Power line communication?

2357


neutral earth resistance testing is it possible for transformer while in load condition

2010


What is the permissible limit of shaft voltage for 6.6 KV motors ? Why? Is there any standard is available?

2730


what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?

8036