11 kv metering is done in my factory.Meter show PF 1.000
but kvarh lag&lead show 24&94 respectively & Avg.PF
is .956 .? is what i do for inproove my PF to 1.000
Answer Posted / vinit patil
Your Meter reads Power factor at load center. In your case
load center might be far away from your tariff meter. Since
your APFC meter shows PF 1.00 but at your tariff meter on
11 KV side p.f still lagging. This happens because of
transformer inductance. Add 10 % KVAR of transformer
capacity directly in ON position. Your problem will go out.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
what is meant by class 1 E in electrical power supply?
Why synchorised generators are used for the production of electricity?
Please define ampere?
DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.
We are planning to synchronized DG's with our captive plant in the event of black start of plant, but before sync we checked voltage of DG with our plant voltage and it varies from 5 V to 450 V. So in this condition how we can sync DG with plant ?
what is the principle of the single phase energy meter? and,what is the advantages and disadvantages of single phase energy meter?
sir i have cleared the apti test of EIL held on 15th march and my interview will be in new delhi on 2nd june.i will be very much helpful if u help me regarding the type of interview questions comes at EIL.(URGENT.........PLZZZZZZZZZZ...............)
Can anyone explain me about the capacitor calculation
What are dcs and plc?
We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?
Is it possible to connect a safety device in to parallel?
i will applied in 1U-1W on 440 volt primary delta side. what is the result of magtic balance test
why normally Generator rating are between 11Kv to 22Kv?
i am studying in final year can i allowed for 23rd UES of Indian army
What is the two pole structure?