11 kv metering is done in my factory.Meter show PF 1.000
but kvarh lag&lead show 24&94 respectively & Avg.PF
is .956 .? is what i do for inproove my PF to 1.000
Answer Posted / vinit patil
Your Meter reads Power factor at load center. In your case
load center might be far away from your tariff meter. Since
your APFC meter shows PF 1.00 but at your tariff meter on
11 KV side p.f still lagging. This happens because of
transformer inductance. Add 10 % KVAR of transformer
capacity directly in ON position. Your problem will go out.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
what happens in the short circuited secondary transformer,if the resistance of the short circuit is increased gradually?
What are the effects of adding a zero to a system?
What are the common sources of energy?
sir my exam is on 19/6/2013 under electrical branch pls send me sample aptitude questions as well as sample technical questions for jindal steel and power company
i want design of D.C.MOTOR 1HP 960RPM AND 2HP 960RPM ITS URRGENT
Define phase cross over?
what is the diference between the 4pole & 6pole DC Motors & what is advantage 6pole over the 4pole ?
size of condotory fron voltage level
why ht motors are star connected?
why 5kW motor becomes unbalance if its relay trip 1st time and its set value is 7.0 A
WHAT IS THE CURRENT CARRYING CAPACITY OF 2.5/3 CORE HI TUFF CABLE,WILL IT SAFLEY CARRY 8.6 AMPS OVER 120 METRES,CAN YOU ALSO ANSWER WITH FORMULA FOR WORKINGS OUT ,THANK YOU 3RDYR APPRENTICE.
Why we find the sensitivity for the CT's to check?
design of IGBT firing circuit for 11KV
How is efficiency of DG set calculated? At many places I found the efficiency to be mentioned in percentage. But at some other places I found kWH/ litres. I want to know how dimensionless percentage value is arrived at?
Whether power factor should be high or low? Why?