11 kv metering is done in my factory.Meter show PF 1.000
but kvarh lag&lead show 24&94 respectively & Avg.PF
is .956 .? is what i do for inproove my PF to 1.000
Answer Posted / vinit patil
Your Meter reads Power factor at load center. In your case
load center might be far away from your tariff meter. Since
your APFC meter shows PF 1.00 but at your tariff meter on
11 KV side p.f still lagging. This happens because of
transformer inductance. Add 10 % KVAR of transformer
capacity directly in ON position. Your problem will go out.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
explain the functions of main isolation switches
What are the different types of LT Cables?
what is EIB lighting control system? what is the advantages of this system?
How to calculate the electrical load for a standard telecom BTS shelter and choose the DG set capacity for the same load?
Why collecting electrode of ESP to be earthed
What is meant by time harmonics and space harmonics?
what is the purpose of bypass mode in energy lighting transformer?
why we need to us lenz's law for synchornous motor
how unidirectional torque is produced in DC motor?
How we can change the direction of rotation of Induction motor? Prove it using graphical
what happens in the short circuited secondary transformer,if the resistance of the short circuit is increased gradually?
What is the difference between Generator Differential Relay and Transformer Differential Relay?
What tests should i carry over on a newly rewinded DC Generator with voltage rating of 38 volts and current rating of 350 amps, to certify that the machine is OK?
what is cathodic protaction?
specific difference of ICT&Auto Transformer