what is the maximum load on for 10 kva & 25 kva transformer
Answer Posted / aruloli
Dear Friend
You forgot to furnish few more data i.e Voltage rating of
primary and secondary.
If i assume Voltage rating for 10 KVA Transformer as 230
V/110 V (Primary/secondary)and considering as single phase .
primary load current is calculated as
P=VI
10*1000(VA)=230*I
I=43.47 A
Secondary current is ,
90.90 A
Considering Transformer as 3 phase, then
P=1.732*v*I
Primary load current is
10000=1.732*230*I
I=25.10 A
Secondary is,
52.48 A
| Is This Answer Correct ? | 35 Yes | 15 No |
Post New Answer View All Answers
i am in need of AC SYNCHRONUS MOTOR 30KW. ANY ONE KNOWS THE MANUFACTURER OF SAME. ALSO MOSFET AC CONVERTER 20KVA CONT.OUTPUT.
delta motor winding resistance I take normally single winding is 2.5, which value is came delta connection ie RY ?
what is effect of length of air gap on performance of dc motor and generator?
A 100W electric lamp is supplied from a 115V, 60HZ source. The peak instantaneous power dissipated in the lamp filament is
how meger function
Either the Armoured Earthing strip of HT 3 core cable have to pass through CB CT or not , why ???
I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.
how single phase preventer works ?
What is the emf equation of a transformer?
when we decide to use soft starter drive or vfd drive in mcc to operate apump?
What is miller crystal oscillator? Explain its operation?
what is high and low cut off voltage of BB and DG at SPS????????
Explain what cmos is and its benefits?
What are approaches to tackle sedimentation problem of reservoir?
Star Delta Diagram with full description