how to calculate knee point voltage of current transformer?
Answer Posted / arvind negi
CT Knee Point Voltage Calculation Sheet
Primary Secondary Volt
Resistance Resistance Length
In MVA In AMP In kV In ohm In
ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection -
1200 1 - - - - -
2 Transformer Rating, MVA 20 - - -
- - - -
3 % Impedance, %Z - - - -
- - - 13.9
4 Voltage of Line Side, KVLV - - -
11 - - - -
5 CT Secondary Resistance, RCT (ohm) - -
- - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm.
- 8.5 -
7 Loop Length of Control Cable - - -
- - - 120
Calculation:
1) Fault Current at Primary Side of CT (kA) =
MVA/*100(%Z*1.732*KLV) 7.55
2) Fault Current at Secondary Side of CT, If (A)=
6.29
3) Cable Lead Resistance, RL (Ohm)=
1.02
4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)
101.2
REMARKS : -
Knee Point Voltage of CT provided by CGL for REF CT
= 115V and for Differental CT = 200V are in order.
| Is This Answer Correct ? | 8 Yes | 4 No |
Post New Answer View All Answers
how diside ct mf exmp.200/5 ct
What is precision of a measurement?
State how to produce a constant rotating field by application of alternating currents to stator armature of a three-phase squirrel-cage induction motor
How to decide the size of the capacitor for a single phase induction motor say 2 HP ??
What test must you do before powering up a circuit that you have been working on?
How does an induction motor start?
how to do the ductor test?
Give some differences between open loop and closed loop control systems.
Differentiate between ideal and non ideal current sources?
suri transmission
any body,pls tell me how to done relay coordination ? how to coordinate by TCC curve?how to read the tcc curve?
hello! sir i did three year of diploma in electrical (2007- 2010) and now i m a student of electrical engineering. sir can i apply for germany visa for study and part tome work over there?
how could we know the size of cable by physical view?
What is shunt voltage and u v voltage witch one best
what is the calculation involved to design the heater to heat 10KL of water in temperature control unit?