Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate knee point voltage of current transformer?

Answer Posted / arvind negi

CT Knee Point Voltage Calculation Sheet



Primary Secondary Volt
Resistance Resistance Length
In MVA In AMP In kV In ohm In
ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection -
1200 1 - - - - -
2 Transformer Rating, MVA 20 - - -
- - - -
3 % Impedance, %Z - - - -
- - - 13.9
4 Voltage of Line Side, KVLV - - -
11 - - - -
5 CT Secondary Resistance, RCT (ohm) - -
- - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm.
- 8.5 -
7 Loop Length of Control Cable - - -
- - - 120


Calculation:

1) Fault Current at Primary Side of CT (kA) =
MVA/*100(%Z*1.732*KLV) 7.55

2) Fault Current at Secondary Side of CT, If (A)=
6.29

3) Cable Lead Resistance, RL (Ohm)=
1.02


4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)
101.2




REMARKS : -

Knee Point Voltage of CT provided by CGL for REF CT
= 115V and for Differental CT = 200V are in order.

Is This Answer Correct ?    8 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why does the radius of armature is less than the radius of pole shoe?

2159


i want to put single phase load on scott connected transformer,eventhough how to balance the transformer.

1838


WHAT IS START TO INDUCTION MOTER IN STAR TO DELTA OF >5HP ?

1873


What test must you do before powering up a circuit that you have been working on?

1861


why genarator genarating voltage 11 KV?

1783


1.how many types of relays? 2.difference between ATS& STS?

2155


How to determine stage of Automatic Power factor controlling Relay(Apfcr)?

2161


what is the IS foe lightning arrester?

2168


What are different types of control systems?

1250


What is marx circuit?

1126


How can calculate the rating of a servo stabilizer for given a specific load

3523


I have an existing old MCCB. ABB Model SACE, the rating are: Ue = 660 volts, Iu =1250 Amps, 3 poles, Ith (max) =800 amps at 45 deg C. I need a circuit breaker for my 3 phase motors, 380 volts 60 hz. the supplier required the minimum ampacity of the breaker to be 911 amps. can i use this breaker with rating of Iu =1250 amps but Ith = 800amps maximum?

2307


what is the difference between 50 hz freq. and 60 hz freq.? which is better and economic in them ?

2284


distribution transformer de-rating formula on over limit iron losses  

2299


100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.

2370