Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate a cable size while load is given in amp or
kw and length is also define.?

Answer Posted / karteek.k

there is an empirical formula to calculate voltage drop for
given cable, when you are given load in amps, i.e
(1.732x1.1xIxLxR)/1000.

1.732- square root of 3(because 3 phase circuit)
1.1- multiplication factor
I- load current in amps
L- length of the cablertee
R/1000 - resistance per kilometer

if u get voltage drop below 5% of the given voltage, i.e
415V, it will be optimum to use that cable otherwise we need
to go for next higher rating.

Is This Answer Correct ?    9 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the effect of higher value of GD???

1807


earth also having a gravitational force (magnetic field of north and south)but it attracts any object compare to this theartifical magnetic cant perform same as earth why?

1984


How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?

1990


what is relation between ct and pt ratio with multiplication factor of a energy meter? is there any other factor on which multification factor depend?

2348


Actually I have a doubt on neutral and earth.we use Ac power without taking neutral by connecting to earth,but at that time does it affects on efficiency of any electrical components or no? If yes how?

1410


at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)

1911


my bachelors was done with EEE now i got admit in NU with CS as course. how to answer this qns 1) why u choose cs? 2) why u changed from eee to cs

1807


12.5 tons a/c is their how much kva generator can recommend to the customer.

2038


which is the best institute for PLC,SCADA,DCS in hyderabad

2364


what is the use of the puls transformer in UPS & how it works???????????

2227


How to Make relay co ordination chart for a Electrical power distribution of a plant

3847


What is the difference between Static and servo controlled voltage stablizer?

2191


single phase power supply give to separate one steel coup with water, what reaction create

2092


How the PF control while running DG set with load

2186


What is the meaning of HT Trivector Meter ?

2471