What is the difference between sensitive earth fault and
restricted earth fault in power transformers?

Answer Posted / raghavendran

Sensitive Earth fault protection: Normally used on systems
where the earth fault current is limited to a very low
value. Scheme consists out of a ring CT (Core Balance CT)
around the three phase conductors, and the relay connected
to the secondary side of the CT. A very low setting is
possible, even sometimes lower then 1% FLA. Need to
coordinate with similar relays downstream. This method is
based on primary current vector addition or flux summation.
The conductor
cables pass through the center hole of the core balance CT.
Secondary current is the system zero-sequence current
3I_0.This scheme provides increased sensitivity with no
false residual currents. However,
care must be taken to prevent false tripping from unbalanced
inrush currents that may
saturate the current transformer core.

residual Earth Fault Relay:Restricted Earth Fault Protection
Is a type of zone of protection, or a differential scheme.
You get two types, low impedance and high impedance. Low
impedance is normally current operated and high impedance
voltage operated. High impedance REF is the most commonly
used. Relay connected in parallel with three phase CTs and
one neutral CT. It will look just for faults inside the
transformer, and need not to coordinate with relays
downstream (can operate very fast). With this kind of
protection you can protect over 90% transformer windings.
Need to use special class CTs, previously called class X
CTs.low impedance REF, are incorporated into some the new
microprocessor relays.

Is This Answer Correct ?    42 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

define as synchronous generator

1688


in a silicon diode we can measure .7v in a voltmeter.but why we can't use this voltage for using?

1455


dear sir/madam i want to get some knowledge about RRB EXAMINATION(section engineer) 1- what is minimum cut off 2- wht portion is major portion . 3- can any body provide Sample paper. thanks & regards ashish

1898


How to do cable earhing? whether by grounding Armour to ground or by running extra G.I wire along with cable? which one is preferred mostly amoung them? If the second one is more preferable how many GI wires to be run along with cable (1 or 2)?

1588


How many types of interlocking use in screw type air compressor,make-Kaser(BSD MODEL)?

1599






what kvrah y we need to take the readind of that

1560


What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2) 

2315


10 Mtr Hight of Lighting Arrestar how much area coverd??

2021


3 phase induction motor connection star or delta while using ac drive motor is .75 to 5.5 kw

1513


what is submersible pump?what is different between motor and sub motor?

1596


what is the calculation involved to design the heater to heat 10KL of water in temperature control unit?

1473


Dear Respected sir how to test ABB REX521 protection relay by relay tester.

2295


any idea abt REVERSE METERING concept.........?

1735


Hoe do calculate the Cable size for Amps rating ?

1687


Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com

1617