Answer Posted / cyber4india
The neutral should be solid and only Link should be provided
in neutral as if fuse is provided, in case of shock, it will
blow due to overload, but the supply will be available
through phase and the purpose of fuse is defeated.
In some case(domestic wiring) the neutral also contains
some potential due to unbalance of load in the supply (3
Phase). This holds true even if you are using the one out of
three phase . The neutral is displaced due to uneven
loading. Hence for any purpose of working, neutral Links
should also be disconnected along with the fuse in phase supply.
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
Please provided formula for calculate the cable size from step up transformer to M.V panel, run overhead aluminum cables, total load is 5mega watt, total length 900 feet.
What happens if i apply 500V to 440V rotary Switch ?
what is earth fault relay 64T, why it is used in main Incomer and neutral CT of Transformer.
What do you understand by oldham's coupling ?
What will happened if the neutral of the (star connected secondry) Xformer disconnected? (if its Above KVA rated one)
how to check three phase motor torque value?
percetans
how do i work out the Amps of a incommer if i am running 1 37 KW motor and a 0,75 KW motor and some solinoids
What are the uses of lead compensator?
how to find the voltage's of a transmission line plzz help with pictures i am not able to understand
Working of microwave oven?
What is an iron loss or core loss pi?
300m long and 30kw inductive loade 3phase supply how many size cable required
what is metering cum synchronizing panel and how it is used?
why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??