How much KVAr bank reqired for 630 KVA transformer on full
load for maintain power factor upto.99
Answer Posted / dhanesh koshti
Capacitor calculation is depends on load. if 630 KVA transformer is loaded fully with load p.f.=1 then no compansation is required but if the same is fully loaded with load p.f. = 0.8 then, kvar required is calculated as below:
KVAR = KW ( tanǾ1-tanǾ2); Ǿ1=old p.f.angle, Ǿ2=new pf angle
= 504 ( 0.75 - 0.14) [ here, KW=504 because, 630 X 0.8 = 504]
= 307.44 KVAR
say, 300 KVAR bank is required at load end for compansation
| Is This Answer Correct ? | 15 Yes | 4 No |
Post New Answer View All Answers
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
How much minimum insulation required between 11kv/3.3kv transformer windings?
what are the preventive maintanance actions taken for air circuit breaker? please answer me
In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?
HAI SENT HPCL APTITUDE QUESTION PAPER, MY EMAIL ID IS angus_eee04@rediffmail.com,angus_eee04@yahoo.com
What is the disadventage of gland earthing(power cable) if any. ?
A 230V dc shunt wound motor has an armature resistance of 0,15Ω.When operating on no load at 650 rev/min the armature current is 6A . The motor takes a full load current of 85A. Calculate the full load speed if the field flux is (i) maintained constant (ii)reduced by 0,03
what will happen if there is a voltage leakage or current leakage in an electrical train
how to convert lv line to hv line and viseversa, any losses will occur during this process
what will happen reduce the transformer voltage from 415v to 406v, is it save the energy,? are this methodis good to reduce the energy.?
Why delta star trformers are used for lighting loads?
what are the basic insulation levels & what its Unit
Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?
How to calculate the fuel consumption for 600kva DG genset which connecting with 25%load?
Why let through energy not considered for ACB breaker while cable sizing?