Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How much KVAr bank reqired for 630 KVA transformer on full
load for maintain power factor upto.99

Answer Posted / dhanesh koshti

Capacitor calculation is depends on load. if 630 KVA transformer is loaded fully with load p.f.=1 then no compansation is required but if the same is fully loaded with load p.f. = 0.8 then, kvar required is calculated as below:
KVAR = KW ( tan&#510;1-tan&#510;2); &#510;1=old p.f.angle, &#510;2=new pf angle

= 504 ( 0.75 - 0.14) [ here, KW=504 because, 630 X 0.8 = 504]
= 307.44 KVAR
say, 300 KVAR bank is required at load end for compansation

Is This Answer Correct ?    15 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

is it possible to turn on the single phase star delta on delay timer using 24 v dc ?

2047


How much minimum insulation required between 11kv/3.3kv transformer windings?

2430


what are the preventive maintanance actions taken for air circuit breaker? please answer me

2035


In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?

2181


HAI SENT HPCL APTITUDE QUESTION PAPER, MY EMAIL ID IS angus_eee04@rediffmail.com,angus_eee04@yahoo.com

2256


What is the disadventage of gland earthing(power cable) if any. ?

2119


A 230V dc shunt wound motor has an armature resistance of 0,15Ω.When operating on no load at 650 rev/min the armature current is 6A . The motor takes a full load current of 85A. Calculate the full load speed if the field flux is (i) maintained constant (ii)reduced by 0,03

2012


what will happen if there is a voltage leakage or current leakage in an electrical train

2020


how to convert lv line to hv line and viseversa, any losses will occur during this process

2070


what will happen reduce the transformer voltage from 415v to 406v, is it save the energy,? are this methodis good to reduce the energy.?

1521


Why delta star trformers are used for lighting loads?

1177


what are the basic insulation levels & what its Unit

2013


Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?

1503


How to calculate the fuel consumption for 600kva DG genset which connecting with 25%load?

2127


Why let through energy not considered for ACB breaker while cable sizing?

2413