2 Diesel Generators 900KVA connected to the bus bar for
essential load as an alternative for power taken from
11/440V 3KVA Transformer supplying this bus bar. my
question here is in the event of power failure on 11KV side
can I feed the power to 11 KV bus by using the same
transformer as reverse feed, what will be the inrush
current???
Answer Posted / joy
Your generator will be damaged. The reason being
that the transformer impedance as well as
impedeance of the entire 11kv side will be loaded
on the generator. Besides the inrush current which
the transformer will take when you charge it. This
will lead to the dropping of pf of the generator,
leading to the heating of its windings. Also you
have to make sure there are no chances of the
"normal" 11kv source being re applied when the
generator is being used to charge the 11kv side. Or
else the generator will experience a shearing of
its rotor.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
What is the difference between rated and per unit in transformer?
Draw torque - speed curve and load curve of induction motor? mark operating point ?
What is the meaning of floating point earthing in battery backed systems ?
HOW TO SET THE EARTH FAULT SETTINGS IN ACB????????????
What are the types of excitation system?
at work i have a genertor/alternater what is the easyest way to work out if it is dc or ac?
Pl.brief me any electrical major fault you have rectified.
percetans
What is frantic effect?
what is load vs Torque curve & why it is used?
Is there any relevant technique to produce power from light and heat energy of the sun simultaneosly from same rays of light?
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
How do we find the rating of a transformer, if it got burnt badly.
how we calculate torque ? how we improve it ?where torque will either motor or generator ?
What are conduct on the testing in cf in ur site?