We have laid the single core Armoured cable 7 nos ( 2 each
phase & 1 neutral ) to cater our electrical load .
the issue is though we have Glanded the cable both the end
also givan the earthing to the panel both the end we are
facing a heavy sparking at the gland side. what could be
the reason.
Answer Posted / shantanu mishra
This is definitely a case of improper earthing. The
substation earthing is poor. The panel and armoring of cable
need to be more strongly earthed. During normal conditions
there would not be any sparking butwhen there is any fault
on 11kv line nearby, the ground potential suddenly rises and
so the panel comes at a high potential and sparking take
place between panels and armoring of cables which are not
getting proper earth.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
What is corkscrew rule?
can anyone explain the star-delta motor control wiring ,which wire go where and how they operate?
oltc of a transformer, how it works? and what are the equipment consist of describe briefly?
What is the meaning of Insulation H for transformers????
How can a equal potential zone be carried out in conductors?
Hi, Next week Iam appearing RRB exam for section engineer. So help me to get modal question papers for this position. Iam very thankful to you. Whether question will be fully techanical format or general form. Please give me a details regarding this exam.
in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?
can you plz send l&t aptitude questions if available its urgent plz plz plz
What is online and offline ups? how does it works?
why dc is used in control circuit for mv & hv switchgear instead of ac
I'm looking for a softcopy manual set for a Credence ASL- 3000. Anyone know where I can get it?
The loads are connected with phase and ground then why current flow as the loads ?
what is the difference between skin effect
In single phase ac ups supply when current is measured with tong tester neutral current is found more than phase current.What is the reason?
100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.