We have laid the single core Armoured cable 7 nos ( 2 each
phase & 1 neutral ) to cater our electrical load .
the issue is though we have Glanded the cable both the end
also givan the earthing to the panel both the end we are
facing a heavy sparking at the gland side. what could be
the reason.
Answer Posted / shantanu mishra
This is definitely a case of improper earthing. The
substation earthing is poor. The panel and armoring of cable
need to be more strongly earthed. During normal conditions
there would not be any sparking butwhen there is any fault
on 11kv line nearby, the ground potential suddenly rises and
so the panel comes at a high potential and sparking take
place between panels and armoring of cables which are not
getting proper earth.
Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
why does the magnetic balance tests at transformer?
Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028
in cvt,there are two windings,1a,1n and 2a,2n.in my one project i use only one winding i.e.1a,1n. the other winding is not in use, so i connect it in open delta and want to close it by ibsertibg thermal resistor. the output of cvt is 132kv/115/sqrt3. plesae tell me exact value of resistor, so i may close it to avoid the resonance phenomenin. send me answer on this email adress please. aetcon-po@aetcon.com
how much UPS neutral erath leakage current.
how we can explain arc heatng?
What do you mean by an instrument transformer?
If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines
How many Zones can be in Conventional type fire alarm system & how can we detect the fire in Conv. type FAS?
what are the specifications we must look at to select a relay for any capacity motor?
what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?
how generator avr give to the input?
what is POTT and PUTT explain?
Differentiate between magnetic field and magnetic flux?
What are the advantages of stationary armature and rotating field system?
Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?