Hello friends i am facing one problem in lighting panel.
Frequently neutral link near to MCCB is burning(firing. What
may be the reason for this one. Please answer me.
Answer Posted / m v v s n murthy
Generally, we will distribute our 1 phase loads equally in 3
phases to get the balanced load and the circuit becomes star
connected. In star connection, there will be no current in
neutral line if the load is balanced.
In the lighting loads also we have to distribute equally in
3 phases. If not, current will increased in neutral.
In your case you did not devide the lighting load to get
balanced star connection, and also the neutral link in your
MCCB under size to carry unbalanced neutral current. And
also there may be loose connection at neutral link.
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing
in cvt,there are two windings,1a,1n and 2a,2n.in my one project i use only one winding i.e.1a,1n. the other winding is not in use, so i connect it in open delta and want to close it by ibsertibg thermal resistor. the output of cvt is 132kv/115/sqrt3. plesae tell me exact value of resistor, so i may close it to avoid the resonance phenomenin. send me answer on this email adress please. aetcon-po@aetcon.com
Why does amplifier gain reduce?
what type of questions are asked and howmwny questions belong this catagory?
How to convert a two phase power into a three phase power in induction machine?
what is the thumb rule for determination resistance of resistor?
what are the factors to be considered while design the breaker either HT or LT??
If we have to feed a housing complex having load 8MVA, than what would be the better option, either we first step down 33kv supply into 11kv & than 430v or we proposed no of 33/.44 kv transformer, also which option is economical?
Mention the disadvantages of low power factor?
what is the standard values(Megger test) of resistances between L&N,L&E and N&E for a system on IEE regulations?
What do you mean by phasors?
How efficiency of thermal plant can be improved?
IF I KNOW THE AREA OF CROSS SECTION OFTHE WIRE , WATTAGE OF THE LOAD ,VOLTAGE SUPPLY WHAT IM GIVING TO THE LOAD AND ALSO POWER FACTOR OF LOAD ....... SO GIVE ME FOR WHAT AMOUNT OF CURRENT I SHOULD USE WHICH TYPE OF CABLE?
How to do bus bar short circuit calculation for 230KV/11kv, 60 MVA Substation?
what is metering cum synchronizing panel and how it is used?