Hello friends i am facing one problem in lighting panel.
Frequently neutral link near to MCCB is burning(firing. What
may be the reason for this one. Please answer me.
Answer Posted / m v v s n murthy
Generally, we will distribute our 1 phase loads equally in 3
phases to get the balanced load and the circuit becomes star
connected. In star connection, there will be no current in
neutral line if the load is balanced.
In the lighting loads also we have to distribute equally in
3 phases. If not, current will increased in neutral.
In your case you did not devide the lighting load to get
balanced star connection, and also the neutral link in your
MCCB under size to carry unbalanced neutral current. And
also there may be loose connection at neutral link.
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
How to calculate approximate load loss of a distribution transformer by knowing %ge imp of transformer?
how desiel generate sart fail of eb?
what is the current density of copper & alluminium.
what is meant by vector group of a transformer? How can it be derived?
What is frantic effect?
How to choose the vector group for the step up and step down transformers??? Tell me the which vector group is suitable for step up and step down transformers and whats the reason to choose and whats the benefits???
how to calculate micom relay earth falt time and current sertting
description with working of all parts of a Diesel generator???????
What does ampere turns shows?
Explain the working of any one cutting machine
What is the test block protection relay if any body know plz explained
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
What is the maximum number of swithes that can be connected in series up to down stream point in an LV Distribution system?
What is the minimum distance to be maintained in between HT panel and LT panel and Instrument panel as per IEC and NEC standards?
Minimum IR value of 1.1 kv grade 3.5c (300, 240,185,150,120,95,70,50,35,25) sqmm Aluminium XLPE cable and 4c (16, 10,6 & 4) sqmm cu arm cable between RY,YB,BR,RN,YN,BN,RE,YE,BE & NE.