what is the formula to calculate kva genset required for a
given load in kw.
Answer Posted / virendra
Kva Required is = KW/0.8( Power factor )
& as the DG set is prefered to run at 80% load of the total
capacity then the Rated capacity is KVA/0.8
If the load is 100 KW rhen KVa is 100/0.8 = 125 KVa & the
rated kva is 125/0.8 = 156.25 KVA say 160 kva D.G set is
required.
| Is This Answer Correct ? | 34 Yes | 6 No |
Post New Answer View All Answers
What was your role in the silicon evaluation/product ramp? What tools did you use?
when will be the iocl interview results i faced interview on 8th september 2008 iam from electrical branch i faced interview for the post of electrical engineer??????????????????????//
Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?
please send me latest & previous years question papers for IOCL Technical level questions
Please send 110 kv sb station full single line drawing(sld)
what is earth fault relay 64T, why it is used in main Incomer and neutral CT of Transformer.
As i want some model question paper in basic computer science and history please send me immediately sir
Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar
XYZ
sir i want previous entrance exam papers for written test
What are the ratings of VCB, MCB, MCCB, SF6, ACB, and OCB?
Draw the line diagram of diffretial relay connected to transformer?
previous year paper of ntpc bhel for degree in electrical enng
what is mean by restructuring power system?
please send me last 5 year interview questions