what is the formula to calculate kva genset required for a
given load in kw.
Answer Posted / virendra
Kva Required is = KW/0.8( Power factor )
& as the DG set is prefered to run at 80% load of the total
capacity then the Rated capacity is KVA/0.8
If the load is 100 KW rhen KVa is 100/0.8 = 125 KVa & the
rated kva is 125/0.8 = 156.25 KVA say 160 kva D.G set is
required.
| Is This Answer Correct ? | 34 Yes | 6 No |