what is pf. how to calculate capacitor bank value to
maintain unity pf.
Answer Posted / vekuva
KVAR= KW(TAN PHI 1 - TAN PHI 2 )
WHERE PHI 1 = EXISTING POWER FACTOR ANGLE i.e., COS^¯1(p.f1)
PHI 2 = REQUIRED POWER FACTOR ANGLE i.e., COS^¯1(p.f2)
p.f 1 = EXISTING POWER FACTOR
p.f 2 = REQUIRED POWER FACTOR
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers