how to calculate the neautral earthing conductor size for a
500kva dg set.
Answer Posted / krl raju
If alternator voltage is considered 415 V, then rated
current of the Alternator is
=500*1000/(1.732*415)=695.6Amps.
Hence we need to select the neutral conductor to withstand
the half of the full load current i.e 350Amps
| Is This Answer Correct ? | 9 Yes | 2 No |
Post New Answer View All Answers
what is spadar bar .why I use in DC generator.
ratings of lightning arrester
two phases with neutral supply can be taken in 3C X 10 sq.mm cable .
what is under coal gassification?
Do any one know exacatly when the results for NHPC held on 8th march 09 for engineering trainees will be released ?. if so please post it, i'm eager to know it.
do anyone out there know where to find a compleete list on acronyms/abbreviations used in offshore electric engineering. MCB - Micro Circuit Breaker, MCCB-Mouldes Case Circuit Breaker, ELCB-Earth Lekage Circuit Breaker, ELMCB- etc.....
A cotter joint is generally used to transmit
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?
what are the application of over current relay?
how to calculate the conductor size for certain KV transmission line and distribution line?
I have 4 DG set with 1500KVA rating. system breakers are 11KV & alternator are 415 Volts. Between alternator & breaker one stepup transformer used. i want to Know what is max. resistance for body earthing & 415 & 11KV V Neuteal earthing. my fault current is 14 times for 2 sec.
What the difference between three phase contactor (coil 110vac) & three phase SSR (control voltage 110Vac)? May I use contactor in place of SSR?
mostly the questions were from machines... d.c. machines, transformer, synchronous and induction all theory paper........ few from power system... but the level of paper was easy.....
explain different losses in a transformer.
How to calculate ant test the burden of Current transformer