IS IT POSSIBLE TO CALIBRATE A LEVEL TRANSMITTER INDICATOR(ABB)
USING HART COMMUNICATOR.? I MEAN TO CHANGE FROM ONE UNIT TO
ANOTHER WITHIN INDICATOR (EG. INCH TO FEET)...? PLZ NOTE
THAT I HAVE MADE THE UNIT CHANGE IN TRANSMITTER USING HART
COMMUNICATOR..BUT WHAT ABOUT THE INDICATOR..?
Answer Posted / sam
Ok I think I understand what you are asking. In most SMART
transmitters you have a digital indication on the
transmitter and you want to change what is displayed on this
indicator. You also said that you have changes the unit of
measure inside the transmitter with the HART, and this also
changed the UOM that is displayed.
There is a different parameter that you need to modify to
change the display. The parameter is normally something like
"set disply" or something like that.
Be aware that it will only display UOM or percentage or
display a switching between the two. What ever you have set
your UOM to inside the transmitter, will be displayed on the
indicator as the UOM. You cannot set the UOM to mmH2O inside
the transmitter and then display mBar on the display.
Also note that for a level application this display is
normally set to percentage and not UOM. If the operator look
at it he needs to see % level and not mm level. In a
pressure, flow or temp applications you want this display to
indicate UOM again.
Good luck
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
any one can send me instrumentation previous interview papers? I prepare for MNC Company Interviews? my mail id- Rakesh.Golla@dodsaldxb.ae , and another mail rakesh.gvk@gmail.com
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????
How do bending tubing provide better measurement than using tubing fittings such as elbows?
What is the purpose of bypass valve across AS valve.
Which type of pressure can be measured by these elements?
pls suggest suitable MOC of diaphragm for pressure measurement of UREA grade solution service fluid.
Give Detail information about plc,dcs,and scada system?
I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.
What is the difference between uv and ir scanners? and what is the workig principle of both
line up procedure for dp type flow transmitter?
What is standard procedure of manual mapping in Radar type level transmitter?
what is the difference between Cv and air consumption? why the customer needs Air consumption details?
How is flow measured in square root?
Why do we have earthing cable in branch cable and shield in the same cable?
Name different types of bourdon tubes.