how can we measure the pressure in underground cooling
water pipeline by using pressure transmitter?what about the
tapping position?
Answer Posted / sam
You can install the PT anywhere on the pipe. It is best to
install on top in crude and slurry application but to
measure water you can install any where, even under the pipe.
If you install on the side or under the pipe fill the
impulse line with water then do a zero on the PT before you
do the final span calibration. Also remember that the
calibration you do on the PT must be exactly the same as to
what your DCS or SCADA faceplate have been scaled to. In
other words if you calibrate the PT for 0 to 20Bar you must
make sure the faceplate in the CCR are also scaled to 0 to
20bar.
Good luck
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
what is the reset offset and control system in instrumentation
Sir, I want junior executive, Instrumentation question papaer for IOCL, Plz send to arabinda.ghosh83@gmail.com
how to check earthing,what is minum ohms for proper earthing
For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.
what are procedure of sox-nox calibration
how we are selecting instuments by differentiating certain instruments in 4 to 20 ma range and certain in 1 to 5 v dc
why orfice is not used for main steam flow calculation
Draw a wheatstone bridge circuit showing supply, meter and 3 wire RTD connection
KAlman filter code for two dimension?
which type of signal used in instrument?
Explain bernoulli’s theorem. State its application.
Q- What are the application in which PNP transistor is preferred over NPN ?
which type of filter gives the constant phase characteristics?