length of 4 core cable 95mm from substation LV VFD panel to
Motor at field approximately 150 meter. Motor stop and power
has been isolated from LV MCC ( Substation )to disconnect
Motor for services. After Motor completed service propose to
reinstall and reconnect Motor Cable, found earth cable
sparkling during touching at metal / motor body.
Inspect by clamp meter found earth cable have current flow
AC 1-2amps and all earth cable at MCC LV also have current
flow as same value. why it is happen?

Answer Posted / mrinmoyboruah

Cable insulation together with cable conductors form
capacitance. On nergising a cable this capacitance gets
charged and cable charging current flows even if no load is
connected at cable end. Similarly when cable is disconnected
from power source it retains the original charging energy
until it finds a conducting path to earth for discharge.
Hence before touching a disconnected cable all its
conductors including metal sheath and armours should be
connected to a earth path so that the stored energy in the
cable gets discharged.

Is This Answer Correct ?    0 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to check the Bushings of the transformer?

1263


why the electrolyte level in lead acid battery is maintained 2.5 cms above electrodes?

1402


What facility we get after CT secondary earthing and how?

1719


Which device of PlC does share load between DG sets when DG are running in perallel?

1553


I am a possesor of c licence from 1993. I forgot to renew during the year 1998. During that time I was working at TNEB to till date. Is there any possibility to get renewed? or to apply for a new one?

1601






In MEP Services what are parts of STP and what are there function?

2938


Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.

1743


Which test will be more severe for VCB?

2219


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1561


if there is nutral in phase why we use earthing wire and grounding? even at fault condition the fault current flows to neutral (it is a lower path)

1333


What are the advantages of hydropower?

655


What is meant by bus bar protection?

641


I am having dual speed motor of cromton greaves make of 3.7 KW -1400 rpm and 5 KW - 900 rpm. Please let me know groups and winding connction for rewinding purpose.

1513


What should be the height of basement according to NBCC code?

1714


how to measure the current by compact digital equipment with dislay which fit inside any equipment

1466