Answer Posted / narenkumar1985
calibration equipment: calibrator with hand-pump
1: connect the calibrator to the transmitter
2: connect the multimeter in series with transmitter to
verify the transmitter o/p in mA
3: Apply the pressure to the transmitter by hand pump
in calibrator
4: compare whether both calibrator and the transmitter
showing the same value.if you applied X psi through the
calibrator then the transmitter should have to show the
same value.If you find any error.Do the zero/span
Adjustment.by adjusting the zero/span screw
increasing/decreasing
5: compare the transmitter and calibrator as per follows
with a desired range of an instrument with o/p 4-20mA
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Pl send the model question paper of mahagenco account officer post
What is first echo & echo window in radar type level transmitter?
Sir , i have completed my M.Sc In Instrumentation and presently working in Maintenance department 3 yrs Exp , is there is any possible for work in offshore ..
what is the process to make control schematic ?
in differential pressure transmitter,min&max pressure range for hp&lp
Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?
What is mean by analytical instrumentation?
sir i m preparing for BARC but i am not getting any papers to prepare for this exam so please send me some sample papers to my i.d for the preparation of barc.
How to calibrate Field bus transmitter? procedure ?
What is ultrasonic flowmeter?
How to Calibrate Level Switch in field
What are different types of valves?
dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.
Who to difference between analog in & analog out in dcs?
what is gas metering system? gas chromatograph? and gas compressors?