Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

A motor works on 30kw.it is working on 440volts.How much
amper will be Required?

Answer Posted / dinesh raj

Voltage =440 V
Power Facter (cos@) = 0.8
Power P = 30kW = 30000W
Formula for 3phase power P = sqr(3)*V*I*cos@
So Current I = P/sqr(3)*V*cos@

I = 30000/1.732*440*0.8
So Required amper = 49.2 A

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How we select the vector group of 3phase power transformer?

2796


How to work meggar?

1916


Name two low frequency oscillators?

1493


We have received supplies of the ordered material. payments against the supplies also released. Where ST paid 4% against form C. Meanwhile it has been observed that 25% of material supplied was defective. Please suggest whether the issuance of C form from our side would be stopped till settlement of liabilities.

1992


in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer 

1861


what happen as when voltage drop(or may decrease) ? in case of atomic base theory?

2081


how the synchronizing is obtained at bus couplers in grid substation? (because there we cannot change the frequency in one of transmission lines like in generator synchronization)

2423


Why insulation level follows this order? transformer < bus bar < circuit breaker & Isolator < transmission line.

2182


Dear all, I just want to ask an expert on this forum for some insights. For the magnetic balance test, when applied voltage on a Delta-Star transformer e.g. Dyn11, the following relationships apply for HV side: 1.  H1-H2 = H2-H3 H3-H1 2.  H2-H3 = H3-H1 H1-H2 3.  H3-H1 = H1-H2 H2-H3 For the LV side also: 4.  X1-X0 = X2-X0 X3-X0 5.  X2-X0 = X3-X0 X1-X0 6.  X3-X0 = X1-X0 X2-X0 Is there a similar pattern for Y-d, Y-Y, D-d? And how about Y-z, D-z, Z-y transformers? I've tested a YNzn5 transformer and for LV side I don't see the pattern. In this particular case I got for LV side the following (see values below): H1-H0  H2-H0  H3-H0    X0-X1  X0-X2  X0-X3 128.0  119.9  7.2      29.2   13.3   15.8 70.7   128.4  59.2     23.4   22.0   3.6 7.2    120.1  128.1    13.4   29.3   15.8 What is the relationship here for LV? For row 1 I see the relationship, for row 3 I also see but it's shifted, but for row 2 I don't see such relationship. Any suggestions, answers, someone?

1910


DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.

2026


Post possible questions for Power Factor Panel FAT / SAT

1449


Advantages/Disadvantages of earthing of neutral bus on MSB instead of separate neutral earthing for transformer/DG sets feeding to MSB

2866


How much of the total hydro power potential has been exploited so far in india?

1174


Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..

2629


Discribe type of fault in DOL and stardelta startor.

2288