how to calculate of which rating transformer should be
selected? take any example
Answer Posted / virendra joshi
usually transformer rating is based on power to be drawn by
the transformer. however few factor is also play a part
like LF, DF...
For Ex say total Connected load is 820 KW
Maximum Demand would be MD= Total connected Load x L.F (0.8)
xD.F (0.7) = 820 x 0.8 x 0.7 = 459 KW
now considering the load at 0.8 leg PF the kva rating of
the transformer is
KVA required = 459 / 0.8 = 574 Kva say .......600 KVA
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
What happens to voltage when current through the inductor is constant?
i have 3500 amp load and select current transformer and perches.how i calculate .please understand
What are the Full Forms of TVM, MTL, CVT ?
howmany electrician should maintain for a 1000 kva used plant... in kerala..
hi this is hema can anyone mail me previous years questions for the APPSC-A.E.E (in electrical stream.) ......thank u.
Define the term factor of inertia.
Define non-touching loop.
What is DTR erection?
I have done my m.tech in electrical engg discipline. Can any one please suggest me how should I prepare for getting into phd in iit or nit.How should I prepare for getting into lecturership
what are inductive and capacitive voltage transformers.what are their applications
Why is tan-delta test and capacitor measurement done on alternator?
How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?
How can ou verify the size of conductor 50Sq.mm ACSR
Dear sir, my knowledge about cable size determination is limited. Though I read examples I could not calculate the Cable size required for electric driven pump 40 KW, 380 Volt, 50 HZ, 50 meter from transformer and it is three phase star delta starting. Please help as there is no one in my surroundings to help.