how to calibate level transmiter ?range -150 to +150.what
is the zero and span?
Answer Posted / sam
This means that your transmitter is capable of measuring a
differential pressure of 300. Whatever this units of measure
is. You can calibrate the transmitter for any of the
following conditions:
LRV = -150 = 0%
URV = +150 = 100%
Therefore span = 300 UOM (units of measure)
or
LRV = 0 = 0%
URV = +150 = 100%
Therefore span = 150 UOM (units of measure)
or
LRV = -150 = 0%
URV = 0 = 100%
Therefore span = 150 UOM (units of measure)
or
You can also calibrate the tx for any span in between this
300 range.
To find the correct Z/S values for your application measure
the distance from the transmitter to zero position on the
vessel and multiply this with the density of the product you
want to measure (LRV). Do the same with your 100% (URV) value.
Good luck
| Is This Answer Correct ? | 21 Yes | 0 No |
Post New Answer View All Answers
what is the protection system in solar turbine compressor
Draw a group of instruments interlocked to a Pump & Motor?
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
What is the meaning of wet leg
please tell me what is a light up procedure of Cfbc boiler and what it's axuillaries of cfbc boiler?
How do you identify between actual alarm and false alarm in a Temperature Transmitter in SCADA based Control System
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
TEMPERATURE VARIATION FOR FREQUENTLY.
How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?
What is difference between Ionization heat and bimetallic heat
what would be the minimum flow rate that we can measure on rotameter..?
Explain bernoulli’s theorem. State its application.
Which type of pressure can be measured by primary elements?
How to Calibrate Vibration Probe (Axial, Redial) in field
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?