why contactor not provided between output of VFD and motor?
Answer Posted / nandan d shanbhag
Due to electromechanical bouncing of the contactor
contacts , voltage spikes are generated which in turn will
result in failure of smiconductors in the drive. However
due to eletrical regulaton if contactor needs to be
provided for electrical isolation then there must be delay
of 1 sec before starting the inverter after contactor is on
and contactor should be made of atleast .5 second after the
inverter is made off.
| Is This Answer Correct ? | 5 Yes | 4 No |
Post New Answer View All Answers
What is the importance of counter based plan & how is it scheduled?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
What is the use of lag compensator?
how to carried out DAR test in 11 KV Alternator ?
How RTCC panel is working and give single line diagram for RTCC with transformer?
I am applying for NTPC examination.Can we please provide previous paper to my mail prasad.chintala108340@gmail.com
Whether IP65 enclosure box blocks ventilation if driver for LED have to enclosed inside IP65 box
How eddy current generation support the idea of train braking?
what is the acceptable value of TAN DELTA and dissipation factor for 11kV, 1.75HP Motor?.
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
what are the safety measures of induction motor?
What is the different types of cable & current capacity of cable
whats the application of voltage regulation? and whats the voltage regulation's device?
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV
Why ground terminal is used in pot meter 10k ohms