Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Please anyone answer my question, what is the difference
between single acting and double acting control valve, in
what condition we better choose single acting rather than
double acting

Answer Posted / sam

Normally a control valve is refer to by it's fail position.
This means "what position will the valve move to should the
supply air or control signal to the valve falls away". This
is important to safe guard the process at various places so
some valves will be fail open and some fail close. In order
to have valve as a fail open or close the valve the actuator
have to be spring loaded. So by having the spring on top or
bottom of the actuator piston, will determine if it will be
a FO or FC valve. This kind of valve is also called single
action since it will only have one output from its
positioner to either the top or bottom of the actuator. The
positioner on the valve is also setup as a single acting
positioner since it will only give a single action to the
actuator, the reverse action will be done by the spring. The
problem with this setup is that it is possible that the
process might be so strong or the pressure so high (during a
blow down or ESD shutdown in the plant) that the spring
might in certain instances be to week to push the valve into
the fail position quick enough, due to the back pressure
from the process and can cause damage to the plant or even a
explosion. To make sure that the valve will go to the fail
position we install a double action positioner with two
outputs. One goes to the top of the actuator and one to the
bottom. This is also very helpful to do very accurate and
stable control on a high flow line since the pressure from
the position do the actual control and not spring control
one way and positioner control the other way as in single
acting control valves. It is also solving the problem that
the valve will now be forced into the fail position by the
spring as well as the positioner supply pressure during a
emergency.
In shutdown valves (open/close ESDV's) the same is true and
sometime at critical and high pressure points we use
hydraulics instead of pneumatics as the double acting agent
to make sure the valve will close during a emergency.
So to summarize the double acting action in ESD and control
valve is just there to make sure the valve will do what it
was designed for. Call it a extra fail safe if you want. In
theory not needed since a single acting valve should do the
trick just as well,but in practice you are at time very glad
you did it especially if you look at the kind of pressures
the valves are working on. With those kind of flows and
pressures you don't want to leave anything to chance.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I want to apply for the universities in US,but i got the GRE score of (650+300=950)TOEFL 69/120.Is this score sufficient for applying universities please i am married i need to go to US because my husband didn't get H1 yet.please send me suggestion

1864


(1) In turbine, what does term CDP, NI, NH, HSSOC, means. (2) What is the purpose of LO overhead tank in turbines.(3) An equipment is certified for EEX, IA, IIC,T6, what do you under stand by this.(4) what is SURGE, and how it is prevented, what is the purpose of bypass valve across AS valve.(5) Give 2 application of quartz crystal used for process parameter measurement.(6) what is meant by cold float of compressor shaft. (7) state four different types of flow measurement. For gas flow measurement mmscfd is the common unit. Expand the unit and specify significance of word S in the unit.(8) what is meant by Gap voltage, in vibration measurement. Normally how much Gap voltage is set and state the reason.(9) what will the new flow factor if D/P transmitter is Re-Ranged from 25” wc to 50” wc.(10) what is the usage of QDV & Volume booster.

4026


how many type of plug are used in pneumatic control valve,name them.

5403


what different types of problems do occur while doing instrumentation commisioning and how to solve them? please explain in detail

1747


What is the difference between modbus,fieldbus & profibus

2401


Hi, Is there any smart plant instrumentation design training institute in Bangalore?

1659


we want to control pump in let pressure and tank (for exp) our inlet line if water cam and pump will on and when our tank will full pump will off also if our inlet pressure low pump will off even tank not full.this pump i want to uses on our water supply line.

1689


How to measure the dust in chimney(spm)?

4086


Tell about your IFFCO plant visit.

2058


which type of signal used in instrument?

9818


I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?

2192


What materials are used in thermo wells?

1152


how to control pid

1903


the output of the common trasmitter protocol in qatar gas are the following

2002


what is output of FOUNDATION FIELD BUS transmitter

2136