Why the Transformer connection is changing in different
transformer?(Like Star & Delta,Delta & Delta,Star &
Star,Delta Star)
From that connection where it is used?
Answer Posted / j.b.
(1) in the star - star connection 57.7% of the line voltage
is impressed upon each winding, but full line current flows
in each winding. power cicruits supplied from a star -star
bank often create serious distrubance in communication
circuits in their vicinity. It is seldom used.
(2) The Delta Delta connction is often used for moderate
voltages. An advantage of this connection is that if one
transformer gets damaged or if removed from service,the
remaining two can be operated in open delta or V-V
connection, but the capacity of the bank is reduced to
57.7% of what it was with all threee phase are in working.
(3)The Star Delta connction is suitable for step down a
high voltage. In this case, the primary is designed for
57.7% of the high tension lines.
(4) Delta Star connction is commonly used to step the high
voltage.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.
Dear All, I am new in construction company , my boss ask a question at time of interview , If we have 60MW generation and Single Power Transformer step-up we have. if CMR 50/60MVA , ONAN, ONAF respectively , is it sufficient or not ? for that much power to transfer,
If we have to feed a housing complex having load 8MVA, than what would be the better option, either we first step down 33kv supply into 11kv & than 430v or we proposed no of 33/.44 kv transformer, also which option is economical?
direction of tarbine& genrator
What is the power requirement of tamil nadu for one month?
Zone of protection and tripping scheme of arc protection relay.
why the name trunking bus PT
can u give me a brief idea about power line carrier communication ??
What are the temperature elements?
How relay works, reverse relay, master relay, os relay, earth fault relay and what is its setting point
I have a 380 KVA DG set. How can i find out 1. My Fuel Consumption per hr ? 2. Electricity produced in 1 Hr. ? 3. If load varies then how does it affect fuel consumption & electricity produced ? Please HELP !!! Really need an answer.
If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?
Explain what is clipper and clamper circuits?
What are IR values and what it should be for coil and for insulator