Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If one d.g. is unable to take full load of system, then
second d.g. will take care of partly Load.for this
condition RPM of both DG set should be equal.By using
Synchronization panel RPM of dg sets are match, is it true?

Answer Posted / vinoth

For Synchronisation the following parameters needs to be matched,
*Phase voltage
*Frequency
*Speed(RPm)
In auto operated DG sets the GCP will take care of matching this parameters, In manual operated DG sets there is an option for matching the Phase voltage and frequency(i.e joystick to adjust voltage and frequency).Since the RPM is depends on the first two factors, the speed will be matched if the first two parameters are same.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the function of RCBO? What are the different sensitivity ratings & each application?

2878


Please brief what is sinewave

2197


describe the fully control circuit diagram of ac drives

1915


Explain Energy and Power signals?

1816


How seriving & testing of the HT & LT breakers are done. What are the standard Ir values on which we can come to know the test is passed or failed?

2099


details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?

1931


PLZ SEND ME SOME UNIQUE PROJECT OF ELECTRICAL ENG (B.TECH)

2010


what is the calculation involved to design the heater to heat 10KL of water in temperature control unit?

2005


why to use freewheeling diode ( diode in revers bias mode) across dc coil

5104


What is Anemometer used to measure?

1181


how to select automotive wire by mathematical equation with given current, vlotage and resistance

2397


how to calculate maximum current

2384


How to calculate no of Lighning arrestors are required for protecting 50mX 50m*20m cubical building and locations of LA?

1887


Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

2027


difference between crane drive and line drive.

1971