I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.
Answer Posted / premgin
See dear the basic soultion to cable size calculatiion in
sismple form can be done like this
Vd= ( mv* I * lenghth)*100/(400*1000)
I u can calualte from the Kw value for the particular pf
simple P/554
L required length
mV is the volatage drop/amp/km that can be obtained for the
particluar size of cable from supplier
eg. for 4cx16 its around 2.5 for most suppliers
100/400 is just amultiplication factor for converting it in
to 3 phase
Now do calulation and check if voltage drop limit is below
2.5 or 4 as per your standards
Simple.
But be cutious this is the simplest method and suitabel
method,many factors like grouping factor,derating
factor,spacing factor,type of laying,etc has to be taken
for apt analysis
Software like E Tap can also be utilised
| Is This Answer Correct ? | 59 Yes | 43 No |
Post New Answer View All Answers
In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?
What is the difference between the relay and the circuit breaker?
In Generator How suction compression power and exhaust works ?
how single phase preventer works ?
Rules and standards of electrical control wiring ?
What is the operating principle of turbo-generator.
We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?
What is Antipumping Function & If we have C.T how we find the Ratio ?
1.dg on load alarm/stop alarm... 2.dg on load. piu alarm alarm kaise chek krte hai
How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter
300m long and 30kw inductive loade 3phase supply how many size cable required
for compensate 315mh inductance ,how many capaciance required?
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
Explain how you intend to work under pressure to meet up with deadline target?
PLZ EXPLAIN CORONA,SKIN,BIRD PALE,SPAN,SAG Effects of power cable.