How do you select a cable size(Cu & Al) for a particular
load?
Answer Posted / mrinal
At first calculate the current of the load, after that
derate the current considering derating factor(depending
on site condition and laying of cable) after choose the
cable size from cable catalog considering derating current.
After that measure the length of cable required from supply
point of load to load poin. Calculate the voltage drop
which will max 3% (resistance and reactance of cable found
from cable catalog of selecting cable) if voltage drop>3%
then choose next higher size of cable.
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
What type of wiring series or parallel is used for conventional and addressable type FAS & why?
i need the details about bhel exam.how to apply for that.please send to my email-id.thenmozhi2k7@gmail.com
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.
In a carnot engine with an efficiency of 40%, the heat rejected to the sink at 27 C is 60 kJ, then the heat supplied in kJ to the engine by the sources is
What must be the minimum distance maintained between 2 Generators as per International standards?
What is a copper loss or i2r loss pc?
what are the parameters plays a major role in Potential transformer Burden calculation??
how many single tension hardware are required on a double circuit transmission tower?
Give idea about General Engineering. From which book i can study this topic. Pl. reply me via email. My email is ravi@bhelhwr.co.in, also give the name of book/website, from where i can prepare it.
WHAT IS FAULT CAPACITY OF HT MOTOR TERMINAL BLOCK? ANY BODY HAVE ANSWER PLZ....POST IT.
i have faced a problem in ro plant grunfos make bm30type pump it is 22kw pump. We start this pump using siemens 3rw 4423-ibc44, 30kw softstarter but this soft starter will frequently failier so we planed to change dol starter. So pls tell anybudy its possible or not.
What is cathode ray oscilloscope (cro)?
Why the efficiency of a three-phase induction is the motor is less than that of a three-phase transformer?
how to calculate mf when meter and cTPT detail are given
Why do you have to use Protecion relay with the function MTB ( Mechanical Trip Button ) for electrical system.