Answer Posted / sanjay singh artemis health i
Mr Ram
its depend on voltage & system is single or 3 phase
but i am giving example for 3 phase 415 V
P= 1.732xVxIxcosQ for 3 phase
so first we need change the KVA to KW
1kva = 1x.8(pf)
=.8kw or .8x1000 Watt
I am giving example .
considering,
V=415VOLTS
3-PHASE
P.F=08
P=1.732xVxIxCOSQ
I=.8x1000/1.732*415*08
I=1.39amps
ok
| Is This Answer Correct ? | 142 Yes | 16 No |
Post New Answer View All Answers
What is dynamo?How it works and what is the function of dynamo in a DG.
why Lightening Arrester Probe sharp at Top of telecom tower.
Hi My dear all Friends, There is a question regarding HVAC Engineering and widely used in Power Projects. Question- What is the diffrence Between REF, SEF and Differential Protection....???? Where REF - Restricted Earth Fault SEF - Senstive Earth Fault.
How to calculate no of EARTH PIT? Describe the formula as per IS standard?
why we testing the core balance of the transformer before comissioning?
how to calculate the lightning arrester conductor @ no of earth pits required
What is reactive power and where it is used.
HOW CAN YOU CALCULATE PRACTICAL EFFICIENCY OF A ASYNCHRONOUS INDUCTIONMOTOR OF 7.5KW,& MOTOR IS RUNNING WITH AVOLTAGE OF 410 VOLTS,& TAKING CURENT OF 13 AMPS
Why computer humming sound occurred in ht transmission line?
why we are using Load factor?
How will A Medium voltage circuit breaker(11 kV voltage level) operate under short circuit fault condition whether It is having short circuit release like Low voltage circuit breaker or relay should be given?
What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.
What is Long rod insulator and it's applications..? merits over the disc insulator ..?
pls tel me the electric train traction motors name plate details like rpm,torue,voltage,amps,watts..ect..
Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar