If DG runing time neutral is disconnected what will be the
effect in Engine and Electricial panel.
Answer Posted / pillay
if the DG is not loaded nothing will happen and there wil be
no damage.While loaded if the load has got no single phase
load also nothing will happen and everything will continue
as normal.If you have connected a load of single phase
nature and if the load is balanced or near balanced then
also if the neutral is removed no damage will happen or you
may not see any changes because the neutral current is
balanced at the phases. but if you have connected an
unbalanced load or the load changes often than the voltages across the phases will be inconsistent.this is a very
damaging situation because the voltage can be as though you
have connected across a 2 phase supply the voltage across
the circuit is determined by the amount of current flow in
each circuit
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
What is synchro?
what is settable hystersis protection? If any body knows plz kindly post the answer..
one split ac how can told of this ac which Tr tell me us
How to calculate multiplying factor of dc energy meter
when will be the iocl interview results i faced interview on 8th september 2008 iam from electrical branch i faced interview for the post of electrical engineer??????????????????????//
what could be the RMS value and average value of a 4 phase sine wave?
how current is reverse from its normal direction during the fault?
why do we not use equivalent voltage source in negative sequence equivalent ckt.
what is meant by LCR meter? where its useful ?
how many Classification of fire extinguisher
why d.c produces corrosion
If a rotary UPS is in line through grid power; What would be the impact on Power Factor if the load through rotary ups is 25% , 50% , 75% & 100%. Will the power factor reduce with less load?
what will be project cost for 100 kv transformer connection under oyt scheme.
What is meant by celling voltage & current in excitor ?
how can calculate 1kva generator running time in 1 liter keroscene