I hv a question regarding power factor improvement just
after transformer. I request you to reply me plzz. thank
you sir.
My friend has a small unit of fabrication. in his factory
the main load is a welding machine, lathe machine, grinding
machine. this load is not continuous type. now our
electricity board has installed 16 KVA, 11000/433 V
transformer for our factory. In the energy meter (trivector
meter) at LV side of transformer, i hv seen power factor
value of 0.15 only when only 3 KW load was flowing. Further
electricity board has suggested to install 4 KVAR capacitor
at LV side after energy meter. Now my question is that if
we permanantly install and switch on 4 KVAR capacitor after
energy meter, during some load on transformer and also
without any load on transformer, wht will be the power
factor shown in energy meter?i dont want to get any penalty
by electricity board, so plz suggest me if i can
permanantly install and switch on the 4 kvar capacitor or
not at LV side of transformer just after energy meter?
Thank you again and awaiting for ur positive reply soon.

Answer Posted / rameez ajmeri

when the capacitor is switched on at load it will improve
the power factor, but you have to take care that the
capacitor is switched on when there is no load on the
transformer...we have to take care about that...

Is This Answer Correct ?    2 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is MEN and RCD related to each other ?? IF yes then how??

1458


What is the emf equation of a transformer?

663


Is the theorem applicable to ac sources?

606


what is the reqirred voltage in HT motor to get full RPM on no load test?

1552


Difference between drift current and diffusion current?

1304






what size steel armoured cable is required to support 1500kva capacity. would 70mm squared be enough or would I need 90 or 120mm squared 3c plus earth

985


How do we find the rating of a transformer, if it got burnt badly.

1049


IN 1000kva transformer where the oil and winding temperature sensors is connected

2056


one split ac how can told of this ac which Tr tell me us

1528


Describe the test procedure to determine the vector group

1590


What do you mean by the zone of protection?

614


Did RMU have ct and pt ?

938


Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example?

1642


WHAT IS DEAD END IN PROTECTION?

2003


can we install HT panel & LT panel side by side or how much clearance is required ?

1080