Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why generally the Rating of Transformers are in additions
of 11 i.e. 11 kVA, 22 kVa, 33 kVA, etc........

Answer Posted / p. h. godavary

Here the question is not correct. Transformer ratings are never in multiples of 11.

It is the Generator voltages that are in multiples of Form factor 1.1(approx.). The voltages are 3300V, 6600V, 11000V. Consequently the normal distribution / transmitting voltages used are 3.3KV, 6.6KV, 11KV, 33KV, 66KV 110KV, .......

Form factor of an alternating current waveform is the ratio of the RMS (Root Mean Square) value to the Average Value of the waveform]. In the case of a sinusoidal wave i.e. , an analogue wave, the form factor is approximately 1.11

Is This Answer Correct ?    34 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can any one tell me about the Extra low voltage systems?From where we give supply to these type of systems??

1857


sir please send me iocl written test paper in my e-mail account. i'll be obliged to you........ thank u roshan

2167


trasnfarmaer core make

1902


how to deside the capacity of chock for drive?

2007


Why CBCT rating is 50/1A

2787


11000volt DG set carnt kaise banvay

1625


How to test the Secure Elite 440 Multi function meter working condition.

2100


Load transfer in 11kv double busbar switchgear - operation.

1902


why HT armoured cable does not glanding

4161


EXPLAIN THE TRANSFORMER MAINTENANCE?

2207


This is reqd for a 1MW Solar power plant..We have 2DC outputs from the solar panels Connected to 2INVERTOR panels.. Output from invertor is 3ph,280v,500kva,50hz.These are connected to individual ACB.This has to be stepped up to 11KV ,1250KVA SYSTEM.Now can I use (1) one more ACBTO GIVE A COMBINED OUTPUT OF 1000KVA,280V & STEP UP THE OUTPUT BY USING a single two winding 3 ph transformer 11kv/1250kva. or (2)use the two outputs and connect to one three winding transformer of above rating..Pls suggestwith details.

2423


full form of electrical?

2655


What should be the Sandwitch type Al. bus bar capacity for 2 M.W.Gen. set, having continuous full load current- 3463 Amps,ambient temp.- 50 Deg. C., Required temp. raise-20 deg.C., it will run 24 hrs, 365 days on full load, required highly reliable.

2617


What will be result if we connect LT votage to the terminal of HT motor?

2088


Why do not we prefer non conventional sources of energy to conventional sources?

1141