can we connect both delta and star to the transformer
secondary and for what reason?
Answer Posted / gopi
suppose in transformer one side of coil of each phase can
connect to ground potential. It means that the insulation
strength of transformer can be reduced compared with Delta
connection . It realize cost down of transformer. Delta
connected coil need same insulation strength on both side
of coil, so it need more cost for insulation. But in Star
connection, harmonics problem will appear. In case of Delta
connection, harmonics current is circulating in delta-
connected coils and not appear in distribution line. If the
harmonic current was there, it will be a cause of over heat
of lead-phase capacitor, lag-phase inductance and
transformaer.
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
how current is reverse from its normal direction during the fault?
could you measure current in parallel?
Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?
Why two phase welding machine is used instead of three phase welding machine.
What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?
what is the function of impulse relay
How can calculate the earthing strip of Copper/GI for rating of 30kV,discharge current 10KA Lightning arrester.
working principle a.v.r. ?
how to calculate fault level?
in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformerÂ
Ceiling Fan and Storage type water heater. Discuss
What is maximum power transfer theorem?
why we are not giving the zone 1 trip command to the master trip relay
when we have to purchase the transformer by own i.e how much load will preferred HT connection?
We have 250 KW x 2 motors, which are load from 25% to 100% varying load in every minute , so how can we compansate the power factor. pl give your opinions on the above subject.