Answer Posted / iamdon
Rating of an alternator or any electrical machine/apparatus
reflects its load carrying capability without
overheating.Temperature rise (major threat to insulation)
arises due to internal loss within the machine.
These internal losses include
1)Copper loss and
2)Core or Fe loss(hysterisis and eddy)
Both losses are independent of power factor.
Copper loss is directly proportionl to I*I
Core loss is function of voltage applied/genetated.
Both loss must be taken into account for rating
purpose.Which is only possible with taking VA which has
nothing to do with power factor.
Author:arbelectbit@yahoo.com
| Is This Answer Correct ? | 45 Yes | 12 No |
Post New Answer View All Answers
Which contains in POLE ASSEMBLY of a 11KV Kirloskar-make SF6 (Model No-FP620A12)? Will u clarify with drawing?
what is the difference between an alternator and a synchronous motor
Why strting torqe high in inducation motor?
During Testing of Maintenance Free Earthing, How deep should be the Spikes of Earth Test Meter should be inserted in the soil(one spike is 15 Meter & Other spike is 30 Mtrs away from the Main Earth Electrode. Because, recently, we observed that when spike is inserted 3-4 Inch in the earth- results are better, If spike is inserted 1 feet deep than results are increasing.
what is the voltage between earth to neutral in lift.
what heppend if we are connected u1-v1-w1 as a star point in the place of u2-v2-w2 in power genration
How many kw will suply from one db
how harmonics generated in induction furnance? how minimise it?
Can anybody just suggest about the scope of Electrical design with ETAP software?Just guide me?
What are the different types of LT Cables?
what is transformor oil gread
What is the estimated total hydropower potential of india?
What is the Nyquist criterion regarding control systems?
What is the Surge suppresor? Why using in a UDB's and How it works?
What do you mean by dependent and independent voltage sources?