sigal phase supply is 230 v ac
two phase supply is 415 v ac
why three phase supply is 415 v ac why not 690 v ac
Answer Posted / vasi
If Phase-Neutral voltage is 230v then Phase-Phase voltage in
3ph system willbe sq.root of 3 X 230v
The 3 ph are displaced 0-120-240 degrees and the Pitagor
Theorem can be used to count up the Line voltage
Another way to count up the Line(Phase-Phase) voltage is to
use vector analysis
1st Phase 0 degree 230+j0
2nd Phase 120 degrees cos120*(230) + sin120*(230) this gives
-115+j199
3rd Phase 240 degrees cos240*(230) + sin240*(230) this gives
-115-j199
in the end ph1-ph2 398v, ph1-ph3 398v, ph2-ph3 398v
Is This Answer Correct ? | 10 Yes | 1 No |
Post New Answer View All Answers
how to calculate fuse rating for a motor
What is Control & Relay Panel? And Remote Control Center?
Whether power factor should be high or low? Why?
In 11/0.414 KV Parralel supply network with Bus tie closed what will be the fault level is it doubled or halved??
why the colour of insultor stack , petticoat is brown. Is it has some technical reason.
whati s the sludge current in ups
Explain the different regions in frequency response?
Difference between a pilot wire and a normal conductor?
What are electric motors?
State the factors, for the choice of electrical system for an aero turbine.
what ispositive, negative, zero sequence impedence?
why does connected a indutor with mnsformeretering core of current transformer ?
What is the formula to calculate the rating of power cable for three phase current.
any earth foult trip the relay but in welding time not trip by earth foult
if in 3-phase system voltage=440V,frequency=60Hz, current=400A. then if it is single phase then current=? and if it is single phasing then current=?