sigal phase supply is 230 v ac
two phase supply is 415 v ac
why three phase supply is 415 v ac why not 690 v ac
Answer Posted / vasi
If Phase-Neutral voltage is 230v then Phase-Phase voltage in
3ph system willbe sq.root of 3 X 230v
The 3 ph are displaced 0-120-240 degrees and the Pitagor
Theorem can be used to count up the Line voltage
Another way to count up the Line(Phase-Phase) voltage is to
use vector analysis
1st Phase 0 degree 230+j0
2nd Phase 120 degrees cos120*(230) + sin120*(230) this gives
-115+j199
3rd Phase 240 degrees cos240*(230) + sin240*(230) this gives
-115-j199
in the end ph1-ph2 398v, ph1-ph3 398v, ph2-ph3 398v
| Is This Answer Correct ? | 10 Yes | 1 No |
Post New Answer View All Answers
If Polarization index of motor 8.75 at 500volts of medium voltage 4.16 KV motor what this mean winding good or bad pl answer if any reffrence book give me the link
explain which quantities change in the starting and the and the running condition in induction motor
please send me the previous year's question papers of jindal GET exams
How could I get a certificate of competency as Electrical Supervisor? I have completed By BTech in Electrical this year(2012) for VJTI Mumbai Maharashtra. Is it compulsory to be produced while joining?
Explain about c.t?
at what basis/standard we have to arrive the current density of aluminium/ copper in busbar?
State the points to be considered for selecting a particular type wiring.
What is difference between Harmonic and Non harmonic Capacitor Bank?
what happen if field of dc shunt motor opens? what is function of putting res. in parallel to one phase of 3 phase IM? the power supplied by 5A source in circuit is given by------Watt.
how was your last weekend.
What is the direction of current flow in ct secondary...means if the current is flowing from P1 to P2 then what will be the direction of current flow in ct secondaryw
What is the restart inhabit setting in ABB spam150c relay (Motor protection relay)
How to calculate the input cable rating for 10kva ups (3phase input and single phase output and also 3phase output, battery rating 65Ah)provide the formula also.thnx
1. The DC generaror,s induced output emf is connected with a DC motor(as load). when increasing the load of the motor by using brake drum or any way. what are the parameters will changes in both motor and generator(voltage, current, resistance, frequency, speed, torque, power, flux etc...) 2. Similarly for AC generator and AC motor 3. similarly if using DC batteries instead of DC generator, What happens?
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?