Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

sigal phase supply is 230 v ac
two phase supply is 415 v ac
why three phase supply is 415 v ac why not 690 v ac

Answer Posted / vasi

If Phase-Neutral voltage is 230v then Phase-Phase voltage in
3ph system willbe sq.root of 3 X 230v
The 3 ph are displaced 0-120-240 degrees and the Pitagor
Theorem can be used to count up the Line voltage
Another way to count up the Line(Phase-Phase) voltage is to
use vector analysis
1st Phase 0 degree 230+j0
2nd Phase 120 degrees cos120*(230) + sin120*(230) this gives
-115+j199
3rd Phase 240 degrees cos240*(230) + sin240*(230) this gives
-115-j199
in the end ph1-ph2 398v, ph1-ph3 398v, ph2-ph3 398v

Is This Answer Correct ?    10 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can some one clearly explain why -48 volt DC use in telecom site????

1634


What is the capacitance values of 132,220,400 & 765 kV current transformer

1865


0.5,1,1.5,2.5,4.0.6.0,10,16 square mm electrical wires how much take maximum current in 50htz

2085


In convertor can we use rectifier thyristor in place of invertor thyristor with explain.

1756


How to calculate the electrical load for a standard telecom BTS shelter and choose the DG set capacity for the same load?

3130


If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.

1379


How can I calculate ISF of current transformer?

3557


What is meant by reset level of the relay?

1155


from which subjects most of the technical que will b asked for hpcl(electrical).pls help me

1946


why starting current is high and resistance is almost 0 during the starting of motor dc motor...?

1687


what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero

2216


what are the different kind of cables used for transmissions?

1163


what is the star delta connetion and how can do it a three phase motor with control witing with picture

2219


How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540

1058


how to check three phase motor torque value?

2304