Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

132 KV TRFO BUSHING BURNT WHEN A 6.6KV HAS BEEN APPLIED
TO IT .WHY .ANY REASON ?

Answer Posted / dinesh lokhande

Let us first understand type of bushing.
Bushings for 132 kV class transformers are generally OIP
(Oil impregnated paper)bushings. However before charging
transformer air release to be done from tranformer tank and
bushings to release trapped air during oil filling. If in
any part of bushing air is trapped then air gets ionised
and provides a path for voltage beakdown resulting in
brsting of bushing due to high voltage stress in bushing.

Some other reason may be dielectric brakdown due to ageing.

Additional information.
Capacitance Tan delta test for OIP bushings can provide
readings of capacitance and tan delta which are indicative
of bushings deilectric health.

Is This Answer Correct ?    14 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Can any one provide the inspection procedure of MIMIC for VFD panel? Details: If someone wants to have a mimic in the VFD panel what are inputs considered for the mimic(like on,off,trip) whether we are able to add speed variation in the mimic(if so how can we get) and what are the parameters to be checked in the MIMIC during inspection?

2204


Can double compression glands be used with regular cables?

2116


in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?

1937


sir i used 3 hp of motor for spraying pump, other home light and other home items which size of allminium pvc wire ix used

1894


why the neutral line is not giving shock to us if we touch it ?

1784


Why is the frequency not changed during transformation of electrical energy in a transformer?

1408


from which subjects most of the technical que will b asked for hpcl(electrical).pls help me

2004


how the characterstics of control valve being done

2084


What is the function of capacitor in electrical circuits?

1048


How can I known multiplying factor .without multiplying table

1800


What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr

1073


How to minimize the eddy current losses?

1188


what is the difference between pvc & fiber glass cables

1567


Explain and give me an example of a time when you had to explain some new procedures to your co-workers for quality service delivery, how did you go about it?

1977


sir, what is the importance of Fault MVA. how to calculate fault mva of 33kv substation connected by 6.5 km line(single circuit with equal spacing) with 110/11kv transformer in 110kv susbstation.the fault mva on 11 kv bus in 110kv susbstation is 208mva.

2964