When charging a 20 MVA , 33kV/6.6kV transformer through
regulated (0-6.6 kV or 0-33 kV) source on no load , what
will be the maximum current drawn by transformer from
source and what sould be the source capacity.
Answer Posted / dinesh lokhande
Actually above answer is not correct as it is the full load
current.No load current is approximately 4 to 5 % of rated
full load current. hence considering the terminals (i.e HV
side or LV side) the current drawn from source will be 4 to
5 % of respective side rated current.
| Is This Answer Correct ? | 8 Yes | 2 No |
Post New Answer View All Answers
What can you contribute to the progress of our Company as an employee if you are selected?
Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?
how does a shunt reactor maintains the bus voltage???
What is Surge Capacitor? Why it is require in Generator Circuit Breaker,inspite of surge arrester?
For RCD (Residual current device) Icu is defined. How i can find Ics for them?
how the characterstics of control valve being done
list of tests to be carried out at manufacturers end while purchasing a step up transformer of 11kv to 66kv ,2MVa Capacity.
HOE WE CAN IMPROOVE BY USE OF CAPACITOR
i have attended the interview on 4th June,08 at Kolkata in IOCL, can anybody tell me what is its result
why occ characteristics curve in not tracing back when we are bringing back the rhoestat?
can u describe the method used for protection of transmission line.
How two nos. 130 kw D.C motor get synchronise using D.C drive.
How energy is generated in hydroelectric power plant?
show the single line diagram of star delta starter with single phase preventer
What is the practical way to calculate the cable size for known ampere load?