i have D.p. transmitter of range 0 to 2540 mmWC, i want to
use this for flow measurement (0 to 500 ltr/hr.) what
should i do?

Answer Posted / k.sreenivasan

Mr.PasavaRaj,
Your question misses a major point.
Do you have a flow sensor (like orifice or annubar etc)
already installed?If yes, Then you have to match the DP
required by the sensor to the transmitter DP Range.Please
note that 2540 mm wc of the transmitter range can be
changed using communicator (If it is HART) based on
transmitter specifcations.Check what is the minimum span
the tranmitter can be calibrated? if that is greater than
the sensor DP, you have to look for another transmitter.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What materials are used in thermo wells?

606


what is The specifications for oriface instalation

1599


the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)

1531


What is the exact differences between HART,FOUNDATION FIELDBUS,PROFIBUS?

2996


Why the ammonia and Nitric Acid level indicators is with millimeter ? and What is the conversion form millimeters that level indicator indicate to weight ?

1202






why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V

1989


if my flow is 20000 m3/h than which range of DPT i have to use????

1280


How can i test procedure grounding for CAT-7 cable? Or How can we test procedure CAT-7 Cable Electrically safe?

2505


what is stroke check for field instument transmetter's & AOV's

1714


need to calculate flow rate with the help of dp range and orifice bore dia and size. range is 0 to 400 inwc and orifice size is 12 inch 150 # rf and bore dia is 7.180 inch. need to calculation for flow rate

874


Explain the working of rota meter.

751


what is the input of digital counter during the the calibration time?

1825


diff between neutral ,ground,phase , earthing and shielding?

1856


can we replace a slot sensor (inductive type) with limit switch (potenial free contact / no-nc type).

1591


what is maxdna ?. explain about the software details.

3888