i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?
Answer Posted / k.sreenivasan
Go to the field and check the local indication in the
transmitter.(normally it is in either engg. units or as
percentage)
If it is zero ,then the problem is in the sensor or
terminal connection, because most of the current generation
transmitters are highly accurate and have longer stability
periods.
Suppose local reading is ok,then check the DCS analog input
card for any fault condition and clear it.Normally this
situation is rare.
| Is This Answer Correct ? | 24 Yes | 1 No |
Post New Answer View All Answers
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
Explain types of valves?
how to relay switch sense the fault?
when a magnet is heated?
Can I calibrate the Electromagnetic Flow Meter on line and How.
what can of fault ofently come in vibration mesurement?
i want formula for flow control.am doing project in flow control using orifice . i know value of the flow level(Q) . upstream(p1) pressure, orifice diameter(Do) , pipe diameter(Di) and oil viscosity(Vi) how can i calculate downstream pressure
what is difference between HOT permit and cold permit
Explain the difference between mmwc and mmwg?
How to fix back the valve actuator stem
How to Calibrate Ultrasonic Level Transmitter in field
what is difference between fork type and capacitance type level switch. where it is using
What pressure results for a flow transmitter of range 0- 180t/h in the dcs and 0-301mbar in the field using square root extraction. Kindly also suggest formulae for the percentages 0,25,50,75,100?
why is not useing in boiler skin thermocople
What are different types of control valves?