i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?
Answer Posted / k.sreenivasan
Go to the field and check the local indication in the
transmitter.(normally it is in either engg. units or as
percentage)
If it is zero ,then the problem is in the sensor or
terminal connection, because most of the current generation
transmitters are highly accurate and have longer stability
periods.
Suppose local reading is ok,then check the DCS analog input
card for any fault condition and clear it.Normally this
situation is rare.
| Is This Answer Correct ? | 24 Yes | 1 No |
Post New Answer View All Answers
selection criteria of control valve? and selection criteria of actuator explain in brief?
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
How can a d.p. Transmitter be calibrated?
In dcs panel we are using diff type of modules ?what is module ? what is the use of modules ?diff type of module?
What is exact difference between the panel earthing and system earthing in DCS system. What is the value of resistence.
What is the main difference between Cavitation and Flashing?
What is the purpose of bypass valve across AS valve.
Explain pH, Conductivity.
what is thermo coupler and how it works
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
Why mixer nd grinder Is example of constant torque load not variable torque load ???
How would you choose differential range?
A DP transmitter is used to measure the level of an open tank. The drain line of the tank is connected to a control valve, and is configured as, if the level of the tank is 90% the valve should get open 10%. And if the tank level is 10%, the valve should get open 90%. Draw wiring diagram and explain how to configure DP transmitter and control valve using HART communicator. If the span error at output is 1%, what will be the %opening of the control valve at 60% level of the tank?
Hi,can anyone help me out with PhD programs related to Instrumentation field?I have a degree in electronic Instrumentation?