Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What are the protections used in a HT breaker to protect
the HT motors.

Answer Posted / sivaraman

We have to use for Motor Protection Relay (SPAM 150C)

1.Short Circuit
2.Excessive Start time
3.Thermal Overload
4.Locked Rotor during running/start up
5.Unbalance/loss of Phase/single phasing
6.Earth fault
7.Loss of Load
8.Temperature supervision of motor
9.Limitation of No. of Starts/Time between starts

All above facilities are available in this relay.

Is This Answer Correct ?    27 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is FM200 Gas??Applications........

2350


what is the AC Plant and how can do the work with parts and picture tell us 150 Tr

2006


Which type of a.c motor is used in the fan (ceiling fan, exhaust fan, pedestal fan, bracket fan etc) which are find in the houses ?

1016


what is the difference between torque induced and torque load?compare them with respect to dc motor?

2280


- two pumps must work with them at the same time but if the first pump start the second pump  must delayed for some time to start  also , with motor rated power = 90 KW and rated voltage = 380 V and rated power factor = 0.85 lag please draw the power and control circuit for it and determine all circuit components parameters that you use it

2731


In PFI plant one stage capacitor connection is directly connected(with out megnetic contact controll). but why?

2267


our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.

2100


what are the breakdown voltage rating of mini- curcuit'transfarmer!

2154


3- What is the target from Zero Impedance, Single Phase Imp., S/C Imp. and magnetic balance tests?

1842


IN induction motor pf is increased using capacitors.what will be the effect on motor and system when very large capacitor is accidently installed and pf goes leading.

2129


What are the no-load losses for the 11000/415V transformer with the following rated capacity? 1.1500 kVA 2. 2000 kVA 3. 2500 kVA 4. 3000 kVA

1743


In electrical locomotive engines, the DC series motors is being used as traction motor. But in new engines like in WAP7 & WAG9 the 3-phase squiral cage induction motors has replaced them. So can someone tell me the advantages of induction motor over dc seris motor in engines points of view....???

2506


What is Servo Ventilated Motor?

2022


what is the ckt diagram of a tubelight and is it the simplest ckt of electrical engineering and also the component?

2370


What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.

2298