how we can calculate cable size of 230v,1 hp single phase
motor ? panel to motor distance is 25 meter
Answer Posted / abokamal
cable design.
first we have to choose CB.
(I)load=P/(V*PF)......... assume pf=0.8
(I)=746/(230*0.8)=4.1 Ampere
(I)cb=(I)load *s.f (FASETY FACTOR)=4.1*1.25=5.1 Ampere
(I)cable=(I)cb/D.F (DERATING FACTOR)=5.1/0.8=6.33 Ampere
from catalouge you can select the cable according to the
current.
you have to see (volt/ampere/meter) to see the voltage drop
limit which according to +-5%
| Is This Answer Correct ? | 9 Yes | 1 No |
Post New Answer View All Answers
what is mean by dual digital protection in the relay field?
Why the efficiency of a three-phase induction is the motor is less than that of a three-phase transformer?
reason of diode failure in alternator
What is a surge supressor why its is used in synchronous generators
if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.
what is difference between isolation and ultra isolation transformer?, what is the method of testing ?
the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?
What is the maximum operating temperature for a thermoplastic insulated cable?
Why computer humming sound occurred in ht transmission line?
What is T’Q and X’Q and X’D ? and what is saturated as well as unsaturated ?
I have a current transformer with 1 main reading meter with transformer outside the building and a control panel having 5 CT reading meters with black round coils inside the building. I want to know, A) when current pass through the Transformers, will the current be reduced or be the same and after that B) when current pass through the CT meters with black round coils, will the current be reduced or be the same. C) in the above process will the reading of the main meter be same or different, from the total reading of all the 5 CT meters.
Can we use Ccapacitive voltage transformer directly for metering purpose?
What is the formula for calculating impedance of transformers connected parallel at fault level 50KA?
What are the common sources of energy?
Is single load(eg: three phase motor) having all the components like positive,negative,zero sequence components during fault condition?