What are methods to avoid the inrush current at the time of
starting of power transformer ?
Answer Posted / priyan
You can reduce the second harmonic by using the DELTA
connection in the CT’s but I prefer to play with the
protection relay parameters, in this case it is better to
control the differential current, there is 2 slopes for the
differential zones, try to increase the slope N01 to get
passing the inrush current.
By filtering the 2 nd harmonics, refer to relay co
ordination and set the values
Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
PLEASE ANYBODY HAVE ELECTRICAL CIRCUIT DIAGRAM FOR CHMER PULSE CD 60M SPARKING MACHINE.PLEASE MAIL ME SUPRIYAAYYAPPAN@YAHOO.CO.IN.
How to reduce -234126219.6403 MVAr generation and by what?
why do we have spikes enough to burn electronic boards, when generators are not grounded
What is real time power factor control panel(RTPFC)?
how line turns ratio changes in 3 phase with change in connection
How we select the vector group of 3phase power transformer?
1) What are your personal strength? 2) What are your personal areas of improvement? 3) What are your expectations from from a particular job? 4) what are your carrier objectives?
what is the electrical?
What is meant by coupling capacitor?
What should be the protection scheme for a 15kw, 3-phase motor working in a lathe machine.
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
How they LT panel busbar size choose
any one guide me to reduce the power factor of diesel Generator from 0.97 Leg to 0.8 Leg.with out any change in my load.
what is the use of current transformer in power transformer secondary side.?its connectyed in WTI
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn