how will i find Transformer rating if supply voltage is
11k.v and how will i find incomer if transformer rating is
12MVA
Answer Posted / subhash sapkal
12MVA Tranformer connect in 11KV linne . 1>primery side
curret is =< 1090A
2> same trasformer in 33KV primery current is =< 363A
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
As a electrical engineer.. what are the basic norms should follow in transformer oil testing.. 1.What is the Electrode type? 2.How long time you will give for oil testing?
how we can calculate 2 phase welding transformer rating or total power?
What is the difference between PLC and Embeded system
HOW TO CALCULATE HV TEST VOLTAGE FOR ELECTRICAL EQPT.
what do you mean by class PS CT and what are technical details needed for calculating it?
what is difference between cpp electrical system and refinery electrical system
What is state space method ? Why its used ? Can it applicable on linear, non-linear, 1st order, higher order, homogeneous, non-homogeneous, open-loop , closed loops , stable & unstable systems ?
what is the requirement regarding earthing of Single conductor with AWA
Explain using drawings what is reverse PID action w.r.t PID controllers.
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
What happen when neutral point connected to core balance current transformer? (Neutral point of an alternator of a 180KVA DG. Neutral point connected to CBCT means enter to the CBCT)
what is the difference between changer, converter and transformer?
with help of neat sketch explain principle of TIG welding process
Hi My dear all Friends, There is a question regarding HVAC Engineering and widely used in Power Projects. Question- What is the diffrence Between REF, SEF and Differential Protection....???? Where REF - Restricted Earth Fault SEF - Senstive Earth Fault.
upto how many load can v connect to stabilizer which is used for tv