Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the type of winding connection( star or delta) in
1HP to 5HP motors. How to check the motor winding
connections( star or delta) if not provided in the
nameplate?

Answer Posted / karl

Most nameplates wont say whether to connect in Delta or
Star but will show a Delta symbol or star symbol with a
voltage rating of current rating next to them. Sometimes a
symbol not even shown but 2 levels or voltage and currents.
This is because this gives you 2 choices of voltages to
connect to. Example if you have a 415V three phase supply
and your motor nameplate shows 230V Delta and 400V Star you
should connect the motor in Star. If it just shows 400V
this usually means you connect it in Delta. If you
connected this motor in Star it would not give you full
output power. These motors sometimes use a star, delta
starter which when in star runs at lower start current.

Is This Answer Correct ?    16 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

before synchronizing an alternator,power factor is leading ,why?

1635


My question is whether bellow formula is correct to find bus size for 46kA for 0.5 second & what is RT in bellow formula. formula to calculate the size of busbar to withstand the thermal stresses due to currents with duration of 0.2 sec to 5 sec. Sp = RT( I x I x t) / K Where Sp – is the cross sectional area of bus bar in millimeters. I -    is the value of AC fault current. t -    is the operating time of disconnecting device in seconds. K –  is the factor depending on the material of the conductor, insulation and initial and final temperature. Value of ‘k’ for copper is 143.

1929


How To increase Knowledge Of boliler regarding To Only Electrical Field..

1668


what is the mechanism of operation of brushless dc motor why is it more wexpensive then ordinary permanent magnet motors

2043


What is the formula to calculate the rating of a three phase air circuit breaker

2397


Name the component u would expect to find in a switchgear assembly?

2083


if there is nutral in phase why we use earthing wire and grounding? even at fault condition the fault current flows to neutral (it is a lower path)

1878


is it possible to turn on the single phase star delta on delay timer using 24 v dc ?

2120


How to setting the volume of RTCC panel AVR (11kv) controller

1629


1. what is usage for power factor in industries?? 2.why we need to monitor power factor??

8389


can any one provide me a connection wiring diagram for a DG set control panel along with BOM?

2254


1.what is the reason for transformer and lightning arrester blast in 33kv system

3147


What are the advantages & disadvantages of a group electrive drive?

2203


what is frequency response?

1189


What is the comparison between 30mA DP RCCB and 100mA DP RCCB and can replace it against 63A MCB

1650