i have one absolute pressure transmitter for the range is
-400mmhg to 400mmhg. If i do the zero trim at atmosphere the
transmitter should be give 4ma or 12ma? which one is correct?
Answer Posted / banerjeenandan
Your transmitter has a range of 800mmhg. The LRV is -400mmhg
and URV is +400mmhg. So at atmosphere you will get 12mA. all
the time, because atmosphere is Zero gauge pressure
(perfectly mid value in between the LRV and URV).
If you do zero trim at atmosphere, it will take "ZERO" with
the atmospheric pressure. The range of the transmitter will
not change. The range will remain 800mmhg. But your LRV will
change to 0mmhg and URV will change to +800mmhg. So in that
case, without any process connection it will give 4mA.
| Is This Answer Correct ? | 25 Yes | 1 No |
Post New Answer View All Answers
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
what is maxdna ?. explain about the software details.
What are primary elements of measuring pressure?
Can any body tell me about SAP MAINTINANCE MODULE. WHAT IS its function and application. And study material Source about it. I shall be very thankful.
Any one can help me to identified, how can we interchange the device in FF
How to calculate P,I&D value in PID controller ?
POSSITIVE PULSE IS APPLIED TO AN INVERTER INPUT.THE TIME FROM THE LEADING EDGE OF THE INPUT TO THE LEADING EDGE OF THE OUTPUT IS 10 ns. THE TIME FROM THE TRAILING EDGE OF THE INPUT TO THE TRYLING EDGE OF THE OUTPUT IS 8 ns. WHAT ARE THE VALUES OF tPLH and tPHL?
why direct mounted pressure transmitters is always installed with DBB ( double bleed block) valve in process line or top of the tanks ?
What are different types of orifice plates? State their uses.
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure
How the warning lamp of a charging-system is activated ?
model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com
Why flow/pressure transmitter before control valve?
How to work temperature gauge?
Whether the DI, DOs shields can be connected with Analog Input Shield Earthpit?