What will be the full load current of 60KVA UPS. Suggest
for this formula.
Answer Posted / muralidhar k.s
Kw=1.732*V*Icos@
Kva=kw/cos@=1.732*V*I
I=1000/1.732*415
I=1.4*Kva
Full load current=KVA*1.4
The full load current for 60 Kva is 84amps.
| Is This Answer Correct ? | 23 Yes | 1 No |
Post New Answer View All Answers
two phases with neutral supply can be taken in 3C X 10 sq.mm cable .
What is the lower limit of break-down voltage of converter transformer.
How o select the electrical fuse?.What are its characteristics.How to select the material od fuse?
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
What is A check, B check, C Check & D check for a diesel Generat
What are the types of the glands and difference between single and double compression type of cable Glands.
If symmetrical fault occurs at the terminal of a synchronous motor then how the motor will act...explain it..
how to produsing geretor power
two way ckt diagram can be drawn by how many ways? give diagram
give some advantages and disadvantages of combiniing the session, presentation, and application layer in the osi model into one single application layer in the internet model
what transformer we used normally and upto which kva?
WHY THREE PHESE SYSTEM VOLTAGE APPLIED IN 440 VOLT
how to calculate cable size in diffrent loads?
how ct burden,magnetising current,ratio and knee point voltage are related & derived
I WANT TO INSTALL LIGHTING ARRESTOR ABOVE 20 FEET HEIGHT INDUSTRIAL BUILDING. NOW IT WAS 15 FEET HEIGHT HOW MUCH DISTANCE IT WILL COVER & HOW TO CALCULAT THE DISTANCE COVER BY THE ARRESTOR