WHAT IS THE DIFFRENCE BETWEEN EARTHED AND UNEARTHED CABLE
(XLPE)?
Answer Posted / c.satheeshkumar
1.For earthed and un earthed XLPE cables, the IS 7098 part2
1985 does not give any difference in specification. The
insulation level for cable for unearthed system has to be
more. In simple statement the manufacturers states that 11
KV earthed cable is suitable for use in 6.6 KV unearthed
system.The process of manufacture of cable is same. The
size of cable will depend on current rating and voltage
level.
what IS specifies and I quote below:
" b) Voltage Grade (Uo/U)
1) Earthed System - 1.9/3.3 kV, 3.8/6.6 kV, 6.35/11 kV,
12.7/22 kV and 19/33 kV.
2) Unearthed System - 3.3/3.3 kV and 11/11 kV.
Note 1 - Cables of 6.35/11 kV grade (earthed system) are
suitable for use on 6.6/6.6 kV (unearthed system) also.
| Is This Answer Correct ? | 44 Yes | 4 No |
Post New Answer View All Answers
What is the high series capacitance winding on high voltage power transformer ?
what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor
please send me last 5 year interview questions
why they were using TRIAC instead relay in some controllers and what is the advantages.
What is the purpose of using busbar mounting fuse?
How to design pavement quality concrete by using C.R.C.P Method
Draw a 230kv two-bus bar system showing the following. 1.Two generators (150MW) each connected through one 15.75/230KV transformers 2. 1 outgoing lines 3. Two 230/130 KV transformers 4. BUS PT's 5. CT
why we used ZNO in Lightning arrester.
From past few months I am getting lagging pf even though sufficient capacitors used in circuit. Where is the problem pls answer
In Generator How suction compression power and exhaust works ?
how many types control panel of a 132/33 kv substation
What is the meaning of loop in transformer
What is star-delta transformer?
What is transient Phenomenon?
What is Primary And Secondary Injection Test of Relay and Other Electrical Devices. How IT is carried out.