WHAT IS THE DIFFRENCE BETWEEN EARTHED AND UNEARTHED CABLE
(XLPE)?
Answer Posted / c.satheeshkumar
1.For earthed and un earthed XLPE cables, the IS 7098 part2
1985 does not give any difference in specification. The
insulation level for cable for unearthed system has to be
more. In simple statement the manufacturers states that 11
KV earthed cable is suitable for use in 6.6 KV unearthed
system.The process of manufacture of cable is same. The
size of cable will depend on current rating and voltage
level.
what IS specifies and I quote below:
" b) Voltage Grade (Uo/U)
1) Earthed System - 1.9/3.3 kV, 3.8/6.6 kV, 6.35/11 kV,
12.7/22 kV and 19/33 kV.
2) Unearthed System - 3.3/3.3 kV and 11/11 kV.
Note 1 - Cables of 6.35/11 kV grade (earthed system) are
suitable for use on 6.6/6.6 kV (unearthed system) also.
| Is This Answer Correct ? | 44 Yes | 4 No |
Post New Answer View All Answers
Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??
can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?
can any tell me why slope 40% and 80% is calculated in differential protection?
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
how to check ac servo motor
How to discuss the phase shift of transformer considering open delta?
What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2)
while starting a liquid starter ,is there any volage drop on water/soda on tank.can we touch the tank on starting?
difference between semiconductor & conductor & insulator?
If I have 3 essential main switch board and 3 incoming electricity ,but only 1 genset running is that possible.
What is 100% protection of generator? Why 100% is not used but 95% is generally used?
Why 3 phase induction motor getting supply in body if one of it's phase is cut
WHAT IS FAULT CAPACITY OF HT MOTOR TERMINAL BLOCK? ANY BODY HAVE ANSWER PLZ....POST IT.
State the formula for overall efficiency of thermal power station
What is Traction? 1KVA Alternator, How much urrent taken?