plz explain TSM and PSM.with example suppose ct ratio is
4000/5 and tsm is .15 and plug is at 3.75 if fault current
is 8000A.so how i find relay oprating time.
Answer Posted / yvb
your PSM set for 3.75 means 3.75 times of your py.
current. if fault current is 3.75 times of 4000 i.e 3.75 x
4000 = 15000 A. your relay will operate in 0.15 sec.(
Primary Injection.)on Secondary we can say 5 x 3.75 =
18.75A flows through ur relay.
Now comming to ur case if fault current is 8000A ie. 2
times of 4000 or u can say 2 times of 5 A.
Then your relay will operate in 0.282 seconds.
Is This Answer Correct ? | 6 Yes | 10 No |
Post New Answer View All Answers
Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632
what is meant by k-rating in isolation transformer?what is k9, k14 stands for?
What is the formula to calculate the rating of a three phase air circuit breaker
hi Is there any possibilities to find out the rotation of a shaft or something else by using electromagnectic waves or by IR rays.If s then can v change the dir., of rotation of the same by remotely?& how? plz dn't any1 say "NO r CAN'T"
State the frequency for rc phase shift oscillator?
i need about 10 years of GATE solved papers in pdf format and even mock tests toooo
What happens if the Capacitive Voltage Transformer Primary neutral is not earthed. There is a CVT between Transformer and source, and the CVT neutral of the transformer is not earthed, does it effect the transformer while charging or does it effect the transformer charging process.
why ct ,cvt should be stored in a vertical position?
What facility we get after CT secondary earthing and how?
Is it possible to operate a synchronous 2-poles turbogenerator with a still-in-place faulted bar but electrically disconnected ???? If yes, should I act on the other phases as well ???
How to maintain ac plant?
Name one of major transformer company in KSA ?
What is the type of feedback used in an op- amp schmitt trigger?
a starter used for squirrel cage induction motor?
How do i right a ladder diagram that has 1 actuator that performs a full stroke followed by a half stroke