Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

HOW TO CALCULATE THE SIZE OF CABLE COPPER & ALUMINIUM

Answer Posted / himadri nayak

Copper Wire
Single Phase/Circuit
Voltage 240
Power(W) 1000
Power Factor 0.8
Resistivity(at 15 c) 1.72E-08
Tempertature 35 C
Resistivity 3.096E-08(for copper)
Length(m) 300(phase+neutral)
Cross section(m2) 0.000006
Resistance 1.55
Load 5.21
Voltage drop 8.06
Percentage 3.36(Do not go above 3 %)
Actual voltage 236.64
Actual Current 5.28

This is a sample of how to calculate wire size for single phase copper wire. If you want contact me for the excel sheet for copper/Al, 3phase/1 phase calculation.

@ himadrinayak@yahoo.co.in

Is This Answer Correct ?    31 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why do we require transformer with less specific weight if supply frequency is increased?

1529


1) Explain why we don't link the two earthing system ht and mv on a pole mounted transformer sub-station.

1743


A 100W electric lamp is supplied from a 115V, 60HZ source. The peak instantaneous power dissipated in the lamp filament is

2330


What are the advantages and disadvantages of the dc motors?

1074


What range of speed can you get with the field control method of speed control of d.c. Shunt motor?

1102


10 tube light connect in mcb breaker.one tube light is fault.so breaker is tribe.how fault is rectified.(using 3wire phase,earth,neutral)

2589


kVA rating of ordinary transformer is increased when connected as an auto transformer because A transformation ratio increased B secondary voltage increased C energy is transferred both inductively and conductively D secondary current increased

2588


What type of core material is used for metering C.T and protection C.T???

2010


Is it possible to connect a safety device in to parallel?

2082


In general bus riser follows the bus section in SWGR. What are impacts if bus section follows bus riser?

1485


List the disadvantages of constant k filters?

1601


i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh

3037


what is the common earth

1022


Alternator rotor earth fault relay circuit

2018


WHAT IS THE PARTIAL DISCHARGE TEST?

2064