Why we use 4 to 20 mA, (This is International Standard)
instaed of this can we use 4-16, or 4-24 or 3- 15 or any
other range
Answer Posted / nagarajan.p
First the question is why can't we use 3~15mA or other
range, here also we can check live zero and also we can go
step current like 3,6,9,12,15(i.e 0%,25%,50%,75%,100%).ok
The reason is the transmitter voltage is 24Vdc , here we
can load max of 600 ohms, for this voltage & load better
range is 4~20.
Why 4 ~ 20 is better since we can convert easily 1~5Vdc by
put 250 ohms.All the controllers and DCS , PLCs are operated
by the input of 1~5Vdc (external or Internal convertion)
| Is This Answer Correct ? | 47 Yes | 5 No |
Post New Answer View All Answers
I want to buy a seal kit of a pneumatic power cylinder.But I don't know it's specification.So please help me to know its specification.
What are de-saturators?
can any one tell me when ongc placement test and its forms is available????/ pls tell me if u know
i need some objective type questions in instrumentation
How to calibration a control valve?
1)How many tpes of vibration probe and how many tpyes of vibration. 2)how we can calibrate a vibration probe with tk3 3)what is RMS value in vibration measuring application and how we calculate it.
What is instrumentation control?
What is the purpose of the analyzer in petrochemical plant?
Explain an adaptive / self-tuning controller’s major draw card.
Where is wet leg is used?
plz send me general of ongc
Instrument QA/Qc what is the project quality plan?conduit inspection RFI. which documents attache with package?
How to erection of DCS Panel at site step by step
what are the diff. in servo and regulatory control?
Why MUX JB's are using only Temperature Element in Fundation field bus?