Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Even motor protection, why motor burn out ?

Answer Posted / atul naik

Its not 100% true. Actually Motor has been protected many
a times before it actually burns. But either we have
ignored the actual reason of tripping by resetting OL
Relay or by removing the Over Load on Motor.
Still Motor Burns. So it is observed that following reasons
are there. 1 Dips in Supply Voltage, 2 Frequent Over Loads
reduces the performance/ sensitivity of OL Relay 3 Short
Ckt Protection is Not there (ANSI 50 & 50N )4 Short Ckt
Protection is Not Fast or delayed ( to avoid Nusence
tripping in Starting )5 Impairing of an Insulation due to
entry of unwanted gases,liquids etc,Reducing the Insulation
Strength of the Motor.,6 Wornout bearings, it will not only
oppose the motion and create resistance but also it
increases the heat / temp. 7 In case of CT Operated
Relays , CTs may reduce senstivity. Now, the cumulative
effect is that Fault Clearing Time is More than the Temp
rise time due to Fault , due to which Motor insulation
fails and motor winding no longer remain healthy ie Motor
burns.

Is This Answer Correct ?    19 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT IS THE DIFFERENCE BETWEEN AN ACB & mccb 7 WHAT IS THE CRITERIA WHEN TO USE WHICH OF THE TWO

2267


what clearance required for 4.5 mva dry type transformer?

1975


What is polar plot?

1120


what is negative and zero impedance in 3 phase induction motor ??

2119


WTA used cb?

1864


how do you test tachos and servos

2083


For RCD (Residual current device) Icu is defined. How i can find Ics for them?

2008


A 100 kVA , 400 v/250 kv testing transformer has 8% leakage reactance and resistance on 100 KVA base . A cable has to be tested at 500 kv using the above transformer as a resonant transformer at 50 hz . if the charging current of the cable at 500 kv is 0.4 A find the series inductance required . Assume 2% resistance for the inductor to be used and the connecting leads . Neglect dielectric loss of hte cable . what will be the input voltage to the transformer ?

5181


what you have to see after one week or month from the day of installation of transformer ?

1661


please send me latest & previous years question papers for IOCL Technical level questions

1832


How does HT work & Voltage required?

2208


how is the testing of an REF relay? what are the test REF circuit having?

1939


Why corona leads to production of Ozone and glow of the color VOILET?

1918


What are the types of the glands and difference between single and double compression type of cable Glands.

2030


how many types of motor can be used in washing machine

2064